Dependency:
Changes only become effective if p0776 does not equal 99.
Refer to: p0788
r0790[0...2]
Test sockets physical address signal value / TestSktsPhyAddrVal
CU_CX32, CU_S
Can be changed: -
Data type: Unsigned32
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Displays the actual value of a signal determined via a physical address.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Only effective when p0776 = 97 or p0776 = 96.
Refer to: p0788
p0795
CU digital inputs simulation mode / CU DI simulation
CU_S
Can be changed: U, T
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the simulation mode for digital inputs.
Bit field:
Bit
Signal name
00
DI 0 (X122.1/X121.1)
01
DI 1 (X122.2/X121.2)
02
DI 2 (X122.3/x121.3)
03
DI 3 (X122.4/X121.4)
04
DI 4 (X132.1)
05
DI 5 (X132.2)
06
DI 6 (X132.3)
07
DI 7 (X132.4)
08
DI/DO 8 (X122.7/X121.7)
09
DI/DO 9 (X122.8/X121.8)
10
DI/DO 10 (X122.10/X121.10)
11
DI/DO 11 (X122.11/X121.11)
12
DI/DO 12 (X132.7)
13
DI/DO 13 (X132.8)
14
DI/DO 14 (X132.10)
15
DI/DO 15 (X132.11)
Dependency:
The setpoint for the input signals is specified using p0796.
Refer to: p0796, p9620
Notice:
If a digital input is used as signal source for the function "STO" (BI: p9620) then it is not permissible to select the
simulation mode and this is rejected.
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital input
DI/DO: Bidirectional Digital Input/Output
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Calculated: -
Dynamic index: -
Units group: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Max
-
1 signal
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Simulation
Parameters
List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 1510, 2020,
2030, 2031, 2100, 2120, 2130,
2131, 2132, 2133
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
FP
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
Terminal eval.
-
1-237