Parameters
List of parameters
Dependency:
The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4098[0...1]
TB30 analog inputs simulation mode setpoint / TB30 AI sim setp
TB30
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Not for motor type: -
Min
-11.000 [V]
Description:
Sets the setpoint for the input voltage in the simulation mode of the analog inputs of Terminal Board 30 (TB30).
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency:
The simulation of an analog input is selected using p4097.
Refer to: p4097
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4098[0...1]
TM31 analog inputs simulation mode setpoint / TM31 AI sim setp
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Not for motor type: -
Min
-20.000
Description:
Sets the setpoint for the input value in simulation mode of the analog inputs of terminal module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The simulation of an analog input is selected using p4097.
If AI x is parameterized as voltage input (p4056), then the setpoint is a voltage in V.
If AI x is parameterized as current input (p4056), then the setpoint is current in mA.
Refer to: r4056, p4056, p4097
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4098[0...0]
TM41 analog input, simulation mode setpoint / TM41 AI sim setp
TM41
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Not for motor type: -
Min
-20.000 [V]
Description:
Sets the setpoint for the input value in simulation mode of the analog input of terminal module 41 (TM41).
Index:
[0] = AI 0 (X523.1/X523.2)
Dependency:
The simulation of the analog input is selected using p4097.
If AI x is parameterized as voltage input (p4056), then the setpoint is a voltage in V.
If AI x is parameterized as current input (p4056), then the setpoint is current in mA.
Refer to: p4097
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
1-820
Calculated: -
Dynamic index: -
Units group: -
Max
11.000 [V]
Calculated: -
Dynamic index: -
Units group: -
Max
20.000
Calculated: -
Dynamic index: -
Units group: -
Max
20.000 [V]
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Access level: 2
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0.000
Access level: 2
Func. diagram: 9663
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]