hit counter script

Siemens SINAMICS S Series List Manual page 135

Hide thumbs Also See for SINAMICS S Series:
Table of Contents

Advertisement

- torques/forces: p0312, p0319
- power ratings: p0307
- masses/moments of inertia: p0341, p0344
All other parameters take into account the replacement/equivalent motor (e.g. r0331, r0370, r0373, r0374).
Dependency:
Refer to: r0331, r0370, r0373, r0374, r0376, r0377, r0382
Caution:
The motors to be connected-up in parallel, must be of the same type.
The mounting regulations when connecting motors in parallel must be carefully maintained!
The number of motors set must correspond to the number of motors that are actually connected in parallel.
After changing p0306, it is imperative that the control parameters are adapted (e.g. using automatic calculation with
p0340 = 1).
Notice:
If p0306 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is appropriately pre-
assigned. This is not the case when commissioning the motor (p0010 = 3).
Note:
Only possible for SERVO!
p0307[0...n]
Rated motor power / Mot P_rated
SERVO
Can be changed: C2(1, 3)
Data type: Floating Point
P-Group: Motor
Not for motor type: -
Min
0.00 [kW]
Description:
Sets the rated motor power (rating plate).
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
p0307[0...n]
Rated motor power / Mot P_rated
VECTOR
Can be changed: C2(1, 3)
Data type: Floating Point
P-Group: Motor
Not for motor type: -
Min
-100000.00 [kW]
Description:
Sets the rated motor power (rating plate).
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
For generators, a negative rated power should be entered.
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Calculated: -
Dynamic index: MDS, p0130
Units group: 14_6
Max
100000.00 [kW]
Calculated: -
Dynamic index: MDS, p0130
Units group: 14_6
Max
100000.00 [kW]
Parameters
List of parameters
Access level: 1
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
0.00 [kW]
Access level: 1
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
0.00 [kW]
1-135

Advertisement

Table of Contents
loading

Table of Contents