p0570
Inhibit list: Number of effective values / Inhib list: Qty
SERVO, VECTOR
Can be changed: U, T
Data type: Unsigned8
P-Group: Applications
Not for motor type: -
Min
0
Description:
Number of parameters in the inhibit list p0571 that should be withdrawn from the automatic motor and closed-loop
control parameter calculation (refer to p0340, p0578), starting from index 0.
Note:
Defines the number of entries in p0571 that should be taken into account. This means that a value of 0 de-activates
the complete list.
p0571[0...49]
Inhibit list, motor/closed-loop control parameter calculation / Inhib list calc
SERVO, VECTOR
Can be changed: U, T
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
The inhibit list contains parameters that should be withdrawn from the automatic motor and closed-loop control
parameter calculation (p0340, p0578).
Values:
0:
640:
1082: Maximum speed
1460: Speed controller P gain
1462: Speed controller integral action time
1470: Speed controller P gain, sensorless
1472: Speed controller integral action time sensorless
1520: Torque limit upper/motoring
1521: Torque limit lower/regenerative
1530: Power limit motoring
1531: Power limit regenerating
Note:
p0570 defines the number of entries (starting at index 0) for which the inhibit should apply. p0572 can be used to
define for which drive data sets the inhibit list should apply.
If a motor data set is entered into a parameter number, then this is not overwritten as soon as only one drive data
set refers to the motor data set (p0186).
p0572[0...n]
Activate inhibit list / Act inhib list
SERVO, VECTOR
Can be changed: U, T
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
Enable ID as to whether the parameters of the inhibit list p0571 should be overwritten when calculating the motor
and closed-loop control parameters for the particular drive data set (index = DDS).
Values:
0:
1:
Note:
0: The automatic calculation (p0340, p0578) also overwrites the parameters of list p0571.
1: The automatic calculation (p0340, p0578) does not overwrite the parameters of list p0571.
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
No parameter
Current limit
No
Yes
Calculated: -
Dynamic index: -
Units group: -
Max
50
Calculated: -
Dynamic index: -
Units group: -
Max
1531
Calculated: -
Dynamic index: DDS, p0180
Units group: -
Max
1
Parameters
List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0