[0] = Line filter
[1] = Line filter, optional
Notice:
When using an Active Interface Module (AIM), it is absolutely necessary that the terminals for the temperature
switch between the Active Interface Module (X121.1/2) and the Active Line Module (X21.1/2) are connected.
Note:
For booksize units, when using an Active Interface Module in p0220[0] it is also possible to use a Basic Filter that is
parameterized in p0220[1].
The setting of the filter capacitance (p0221) and filter resistance (p0222) - derived from p0220[0, 1] - are required in
the closed-loop voltage controlled mode to automatically compensate the filter reactive current.
For two power ratings, the same line filter is used for both power ratings.
AIM: Active Interface Module
p0221[0...1]
Infeed filter capacitance / INF C_filter
A_INF
Can be changed: C2(1)
Data type: Floating Point
P-Group: Converter
Not for motor type: -
Min
0.00 [µF]
Description:
Sets the filter capacitance of the line filter (connected in a delta configuration).
Index:
[0] = Line filter
[1] = Line filter, optional
Note:
When a Siemens line filter is used (p0220) this parameter is automatically preset with the correct value.
For a parallel circuit, the value corresponds to the capacitance of a power unit.
Index 0 refers to the first line filter from p0220[0].
Index 1 refers to the optional second line filter from p0220[1].
p0222[0...1]
Infeed filter resistance / INF R_filter
A_INF
Can be changed: C2(1)
Data type: Floating Point
P-Group: Converter
Not for motor type: -
Min
0.00000 [Ohm]
Description:
Sets the filter resistance in series with the filter capacitance.
Index:
[0] = Line filter
[1] = Line filter, optional
Note:
When a Siemens line filter is used (p0220) this parameter is automatically preset with the correct value.
For a parallel circuit, the value corresponds to the resistance of a power unit.
Index 0 refers to the first line filter from p0220[0].
Index 1 refers to the optional second line filter from p0220[1].
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Basic Line Filter Booksize 400 V 80 kW (6SL3000-0BE28-0DAx)
Basic Line Filter Booksize 400 V 120 kW (6SL3000-0BE31-2DAx)
AIM 400 V 16 kW (6SL3100-0BE21-6AB0)
AIM 400 V 36 kW (6SL3100-0BE23-6AB0)
AIM 400 V 55 kW (6SL3100-0BE25-5AB0)
AIM 400 V 80 kW (6SL3100-0BE28-0AB0)
AIM 400 V 120 kW (6SL3100-0BE31-2AB0)
Calculated: -
Dynamic index: -
Units group: -
Max
100000.00 [µF]
Calculated: -
Dynamic index: -
Units group: -
Max
100.00000 [Ohm]
Parameters
List of parameters
Access level: 3
Func. diagram: 8950
Unit selection: -
Expert list: 1
Factory setting
0.00 [µF]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00000 [Ohm]