p0738
BI: CX signal source for terminal DI/DO 8 / CX S_src DI/DO 8
CU_CX32
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 8 (X122.7).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.8 = 1).
DI/DO: Bidirectional Digital Input/Output
p0739
BI: CU, signal source for terminal DI/DO 9 / CU S_src DI/DO 9
CU_S
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 9 (X122.8).
Notice:
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.9 = 1).
DI/DO: Bidirectional Digital Input/Output
p0739
BI: CX signal source for terminal DI/DO 9 / CX S_src DI/DO 9
CU_CX32
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 9 (X122.8).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.9 = 1).
DI/DO: Bidirectional Digital Input/Output
p0740
BI: CU, signal source for terminal DI/DO 10 / CU S_src DI/DO 10
CU_S
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 10 (X122.10).
Notice:
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.10 = 1).
DI/DO: Bidirectional Digital Input/Output
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Calculated: -
Dynamic index: -
Units group: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Max
-
Parameters
List of parameters
Access level: 1
Func. diagram: 2230
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2030, 2130
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2230
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2031, 2131
Unit selection: -
Expert list: 1
Factory setting
0
1-229