Commissioning (software)
2.7 Commissioning modes
2.7.2
Quick commissioning
Description
If there is still no appropriate parameter set for the drive, then a quick commissioning must
be carried-out for the closed-loop vector control and for the V/f control including a motor data
identification routine. The following operator units can be used to carry-out quick
commissioning:
• OP (option)
• PC Tools (with commissioning program STARTER).
When the quick commissioning is carried-out, the motor-drive inverter is basically
commissioned; the following data must be obtained, modified or entered before quick
commissioning is started:
• Enter the line supply frequency
• Enter the rating plate data
• Command/setpoint sources
• Min./max. frequency or ramp-up/ramp-down time
• Closed-loop control mode
• Motor data identification.
Parameterizing the inverter with OP
The frequency inverter is adapted to the motor using the quick commissioning function and
important technological parameters are set. The quick commissioning shouldn't be carried-
out if the rated motor data saved in the inverter (4-pole 1LA Siemens motor, star circuit
configuration inverter (FU)-specific) match the rating plate data.
Warning
The motor data identification routine MUST not be used for loads which are potentially
hazardous (for example, suspended loads for crane applications). Before the motor data
identification routine is started, the potentially hazardous load must be carefully secured (for
example, by lowering the load to the floor or by clamping the load using the motor holding
brake).
The possible rating plate data is shown in the figure below. The precise definition and
explanation of this data is defined in DIN EN 60034-1.
2-18
Operating Instructions (Compact), 04/2006, A5E00766042B AA
Control Units CU240S