hit counter script

Reset Parameters To Factory Settings - Flow Chart - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

2.7.11

Reset parameters to factory settings - Flow chart

Reset to the factory setting
Parameter or action
P0003 = 1
P0004 = 0
P0010 = 30
P0970 = 1
BUSY (on OP)
Progress bar (STARTER)
Note
The following parameters will not be changed with a factory reset:
P0014 Store mode
P0100 Europe / North America
P0201 power stack code number
Data depending on actual Power module
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
Warning
Safety-Integrated parameters
When using CUs without safety-integrated functions, only the factory reset with P0970 =
1 must be taken into account.
When using CUs with safety integrated functions two reset methods are available:
• P0970 = 1 resets only non fail-safe function relating parameters (application
parameters).
If a factory reset with P0970 =1 is performed on a Safety-Integrated control unit all
application parameters will be reset, previous parameters settings regarding fail-safe
functions remain unchanged. This means, no acceptance test has to be performed.
• P0970 = 10 (password protected) resets only fail-safe function relating parameters
If parameters regarding fail-safe functions must be changed, an acceptance test has
to be performed.
Description
User access level*
1: Standard: Allows access into most frequently used parameters.
Parameter filter
0: All parameters
Commissioning parameter*
30: Factory setting
Factory reset*
1: Parameter reset to the default values
The inverter carries-out a parameter reset (duration, approx. 10 s) and then automatically
exits the reset menu and sets
P0970 = 0: Disabled
P0010 = 0: Ready
Commissioning (software)
2.7 Commissioning modes
2-53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics cu240sSinamics cu240s dpSinamics g120

Table of Contents