Table 32. System commands (continued)
setHistSyst
Modify a history system setting.
Syntax
setHistSyst [option]
Options
Interval = xx
Example
#> setHistSyst Interval=12
getEnvSyst
Read an environment system setting.
Syntax
getEnvSyst [option1] [option2]
Options
Interval | Delimiter
Example
#> getEnvSyst Delimiter
setEnvSyst
Modify an environment system setting.
Syntax
setEnvSyst [option1] [option2]
Options
Interval = xx
Delimiter = Comma | Tab
Example
#> setEnvSyst Delimiter=Comma
Shutdown commands
Use the shutdown commands in the following table to define the UPS behavior
during a shutdown.
Table 33. Shutdown commands
getShutdown
Read a shutdown setting.
Syntax
getShutdown N [option1] [option2]
Options for
Options for N=1:
N = 1 | 2 | 3
iName | RunTimeToEmptyLimit | RemainingCapacityLimit | ShutdownTimerSelected |
ShutdownTimer | ShutdownDuration | RestartLevel
Options for N=2 or 3:
iName | ShutdownTimer | RemainingCapacityLimit | ShutdownDuration | StartupTimer
Example
#> getShutdown 1 ShutdownDuration
setShutdown
Modify a shutdown setting.
Syntax
setShutdown N [option1] [option2]
Options for
Options for N=1:
N = 1 | 2 | 3
iName = "xx..xx"
RunTimeToEmptyLimit = xx
RemainingCapacityLimit = xx
ShutdownTimerSelected = 0 | 1
ShutdownTimer = xx
ShutdownDuration = xx
RestartLevel = xx
Options for N=2 or N=3:
iName = "xx..xx"
ShutdownTimer = xx
RemainingCapacityLimit = xx
ShutdownDuration = xx
StartupTimer = xx
(10 to 2147483647 in seconds)
(10 to 2147483647 in seconds)
(0 to 99999 in seconds)
(0 to100 in seconds)
(0=No, 1=Yes)
(0 to 5999940/60 in minutes)
(120 to 9999 in seconds)
(0 to 100%)
(99 to 99999 in seconds)
(120 to 9999 in seconds)
(0 to 65535 in seconds)
Chapter 4. Using the Telnet, SSH, and CLI
(0 to 100 in seconds)
57