The status of each output is indicated by an Off icon (red) or an On icon (green).
The shutdown sequences allow time for the registered servers to shut down without
losing data (see "Shutdown parameters" on page 31).
The main output has priority over the load segments. Shutdown of the main output
causes the load segments to shut down. Load segments can be started only if the
master output is on.
In the Control column, select one of the following commands for each output, and
click Execute to initiate the selected commands:
Safe power down
Immediately start a sequence to turn off output power. The supplied
systems are shut down, and the output power is turned off.
Safe power down & reboot
Immediately start a sequence to turn off and then restore output power. The
supplied systems are shut down, and the output power is turned off. Then,
the restart sequence is initiated at the end of the time delay that you
specified in the Toggle Duration parameter. The output status is updated.
Immediate On
Immediately start a sequence to turn on output power and start the supplied
systems.
Delayed, safe power down
After the number of seconds that you specified in the Off Delay parameter,
start a sequence to turn off output power. The supplied systems are shut
down during the shutdown sequence, and the output power is turned off.
Delayed, safe power down & reboot
After the number of seconds that you specified in the Off Delay parameter,
start a sequence to turn off and then restore output power. The supplied
systems are shut down, and the output power is turned off. Then, the
restart sequence is initiated at the end of the time delay that you specified
in the Toggle Duration parameter. The output status is updated.
Delayed On
After the number of seconds that you specified in the On Delay parameter,
start a sequence to turn on output power and start the supplied systems.
In the Off Delay column, specify the value that is used by the Delayed, safe power
down and Delayed, safe power down & reboot commands to allow time for the
registered servers to shut down without losing data (see "Shutdown parameters" on
page 31).
In the Toggle Duration column, specify the value that is used by the Safe power
down & reboot and Delayed, safe power down and reboot commands.
In the On Delay column, specify the value that is used by the Delayed On
command.
Click Save to save the Off Delay, Toggle Duration, and On Delay parameters.
Note: For security, you must click Save and enter the administrator login and
password to save modifications or run commands. The default login is
USERID (all uppercase), and the password is passw0rd (all lowercase with a
zero, not the letter O).
Chapter 3. Using the network management card web interface
29