General Operation
7.5 Volume
Example:
To configure volume for a vessel with a half-sphere bottom, set the following:
Parameter
Vessel Shape (2.6.1.)
(Page 184)
Maximum Volume
(2.6.3.) (Page 186)
Dimension A (2.6.4.)
(Page 186)
Note
• The default reading changes to a range from 0 to 100
• The process empty value is still measured to the bottom of the vessel (Low Calibration
Point (2.2.1.) (Page 176) plus any Far Range (2.2.5.) (Page 177)), not the top of
Dimension A.
96
Dimension A
Sample Value
HALF SPHERE BOTTOM
100
1.3
Description
selects the correct vessel shape
sets maximum volume at 100 (defined in Vol-
ume Units (2.6.2.) (Page 186))
sets dimension A to 1.3 m
Operating Instructions, 04/2021, A5E33329501-AG