Parameter reference (LUI)
9.4 Communication (4.)
Discrete Input 2 (3.4.2.2.)
Disables simulation of Discrete Input 2, or sets behavior of DI during simulation.
Options
9.3.4.3
Pump Activations (3.4.3.)
Sets how physical relays (that are assigned to pumps) will behave in simulation mode.
Options
9.4
Communication (4.)
9.4.1
Device Address (4.1.)
Sets the device address or poll ID on a HART network.
Values
To reset Device Address via SIMATIC PDM:
• Open the project in Process Device Network View then right-click on the device.
• Go to Object Properties and open the Connection tab to access the field Short Address.
Note
The following list of parameters are available in PDM. Unless otherwise stated, the options
are displayed in integer format (as required by HART communications).
Manufacturer's ID
Read only. Numerical code that refers to the manufacturer of the device (e.g. 42, which
refers to Siemens).
Device Id
Read only. Unique identification of the device by manufacturer and device type.
Product Id
Read only. Unique identification of the product by model number.
264
*
DISABLED
ON
OFF
*
DISABLED
ENABLED
Range: 0 to 63 (Set within range of 0 to 15 if HART 5 master used.)
Default: 0
DI is not simulated
DI is simulated to be ON
DI is simulated to be OFF
Pump relays are not activated in simulation
Pump relays are activated in simulation
Operating Instructions, 04/2021, A5E33329501-AG
SITRANS LUT400