Summary of Contents for Siemens SITRANS LUT400
Page 1
Communications For SITRANS LUT400 (HART) Manual 02/2014...
Page 2
The user is responsible for all changes and repairs made to the device by the user or the user’s agent. All new components are to be provided by Siemens Milltronics Process Instruments. Restrict repair to faulty components only.
Table of Contents Table of Contents .......................i Introduction ........................1 Overview ..............................1 Safety Notes ............................1 The Manual ............................1 Technical Support ..........................2 Service & Support on the Internet ..................2 Additional Support ........................2 Abbreviations and Identifications ...................3 Operation via SIMATIC PDM 6 (HART) ................5 Features ............................5 Functions ............................5 SIMATIC PDM version .......................6...
The Manual This manual provides information on the use of SITRANS LUT400 with various remote communications software packages noted above. The manual is designed to help you get the most out of your ultrasonic device when used in conjunction with a remote communications tool.
• Information about field service, repairs, spare parts and lots more under "Services". Additional Support Please contact your local Siemens representative and offices if you have additional questions about the device. Find your contact partner at: Local contact person (http://www.siemens.com/automation/partner) Page 2 COMMUNICATIONS FOR SITRANS LUT400 (HART) –...
LUT400 Liquid Crystal Display Local User Interface software package used to SIMATIC Process Device Manger commission and maintain SITRANS LUT400 Primary Measuring Device Primary Value measured value Universal Serial Bus A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 3...
Parameters are identified by name and organized into function groups. The menu structure for SIMATIC PDM is almost identical to that of the SITRANS LUT400 LCD. See LCD Menu Structure in LUT400 operating instructions for a complete list of parameters in chart format.
As a guideline to locate the correct EDD, the major and minor numbers should match between the EDD revision and the Firmware revision in the device (e.g. major and minor numbers in bold text: 1.00.00-04). To check it in PDM, go to SITRANS LUT400 HART > Identification > Device. matching Firmware...
Please consult the operating instructions or online help for details on using SIMATIC PDM. (Application Guides for setting up Siemens HART instruments with SIMATIC PDM are available on our website: www.siemens.com/processautomation.) If you have not already done so, check that you have the most up-to-date Electronic Configuring a new device Device Description (EDD) for your instrument.
Page 12
• Click on BACK to return and revise setting or Cancel to exit the Quick Start. Open the Device menu in SIMATIC PDM and select the Quick Start applicable to your application: Quick Starts Page 8 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Italian, Portuguese and Russian are not supported in SIMATIC PDM for Note: SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese. After making all desired changes, click on Next.
Page 14
Click on Next. Step 3 - Ranges Modify parameters as required. Click on Next. Step 4 – Summary Check parameter settings, and click on Cancel to abort, or apply your changes. Page 10 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 15
Transfer to save your changes and transfer settings to the device. The message Quick Setup was successful will appear. Click on OK. Configuration via the SIMATIC PDM Quick Start Wizard for a Level application is now complete. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 11...
Italian, Portuguese and Russian are not supported in SIMATIC PDM for Note: SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese. After making all desired changes, click on Next.
Page 17
The vessel shapes shown are predefined. To describe a more Quick complex shape see Start (Volume - Linearization) on page 15. Select a Vessel Shape for your Volume application. Click on Next. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 13...
Page 18
Transfer to save your changes and transfer settings to the device. The message Quick Setup was successful will appear. Click on OK. Configuration via SIMATIC PDM Quick Start Wizard for a simple Volume application is now complete. Page 14 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
You can accept the default values without modification (TAG, Long TAG, Descriptor, Message, and Installation Date fields can be left blank), Click on Read Data from Device (if this is not the first time running the Quick Start Wizard). A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 15...
Page 20
Italian, Portuguese and Russian are not supported in SIMATIC PDM for Note: SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese. After making all desired changes, click on Next.
Page 21
Make a selection and click on NEXT. Step 4 - Ranges Modify parameters as required. Click on Linearization to set breakpoints. In the Linearization window click on the appropriate Breakpoint tab to open the dialog window. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 17...
Page 22
The message Quick Setup was successful will appear. Click on OK. Configuration via SIMATIC PDM Quick Start Wizard for a Volume application with a complex vessel shape is now complete. Page 18 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Italian, Portuguese and Russian are not supported in SIMATIC PDM for Note: SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese. After making all desired changes, click on Next.
Page 24
Select a Primary Measuring Device for your Flow application and change Units if desired. Additional parameter default values appear depending on the Primary Measuring Device selected. Modify as required. Click on Next. Page 20 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 25
Transfer to save your changes and transfer settings to the device. The message Quick Setup was successful will appear. Click on OK. Configuration via SIMATIC PDM Quick Start Wizard for a Flow application is now complete. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 21...
Enable pump control, and select which relay is wired to Pump 1. (The relay for Pump 2 will be set automatically based on your selection for Pump 1.) Click on Next. Page 22 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 27
Enter the start level (ON Setpoint), and stop level (OFF Setpoint) for each pump, then click on Next. Step 4 – Summary Check parameter settings, and click on Cancel to abort, or apply your changes. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 23...
Many parameters are accessed via the 5-level menu in PDM. See pull-down menus below for the others. Launch SIMATIC PDM, connect to SITRANS LUT400, and upload data from the device. Adjust parameter values in the parameter value field and then press Enter. The status fields read Changed.
Parameters accessed via pull-down menus You have access to a number of functions via pull-down menus from the menu bar under Device or View. For a complete list, see pull-down menus below. pull-down menus A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 25...
Page 30
Loop-Test Master Reset Reset Min/Max Temperatures Update Reset Totalizers * Configuration Flag Reset HART Communication * Selected menus visible only if Product Capabilities set to Pump and Flow or OCM. Page 26 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
• on page 28 TVT Shaper • on page 29 Auto False Echo Suppression • on page 30 Echo setup • on page 32 SITRANS LUT400 (HART) Operating Instructions (7ML19985MV01) A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 27...
Page 32
View Saved Echo Profiles To view saved profiles, click on Saved Echo Profiles, and select a profile. The selected profile with associated parameter values will display. Page 28 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 33
Alternatively, enter values for Point and Offset directly into the dialog boxes. • Press Transfer to Device. Note: • If steps are repeated (measurement taken a second time) without first transferring shaping adjustments to the device, initial shaping will be lost. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 29...
Page 34
Enter the value for Auto False Echo Suppression Range and select On. Click on Learn. The message appears: ’This will learn a new TVT. Once done it cannot be undone’ . Click on OK. SITRANS LUT400 (HART) Operating Instructions (7ML19985MV01) Page 30 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 35
Before Auto False Echo Suppression default TVT material level Hover false echo Level echo marker After Auto False Echo Suppression material level Auto False Echo Suppression Range default learned TVT echo false echo marker A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 31...
(Required)/Reminder 2 (Demanded) Click on Write. Click on Read, to see the effects of your modification. Click on Snooze for 1 year to add a year to the Lifetime (Expected). Page 32 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 37
Totalizer Multiplier Set Pump Runtimes Set runtime for each pump. Open the menu Device – Set Pump Runtimes to view: • Run Time Relay 2 • Run Time Relay 3 A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 33...
Page 38
Open the menu Device – Product Capabilities. Select product capability from the drop-down box, or click on button Read Product Capabilities from Device. Click on OK to save. Page 34 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 39
After the reset is complete upload parameters to the PC/PG. (If you are performing a reset after replacing the device with a different device, do not upload parameters to the PC/PG). SITRANS LUT400 (HART) Operating Instructions (7ML19985MV01) A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 35...
To compare outputs in real time, open the menu View – Process Variables and click on the Overview tab to see reading (level, space, distance); analog output; range and loop current. Page 36 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 41
Temperature To see current, highest and lowest process temperatures, click on the Temperature tab. Totalizers To see OCM Flow and Pumped Volume Totalizers, click on the Totalizers tab. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 37...
Page 42
Level, Space, Distance, Volume or Flow. Discrete Inputs and Relays The Discrete Inputs and Relays tab displays programmation and state for DIs and relays. SITRANS LUT400 (HART) Operating Instructions (7ML19985MV01) Page 38 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 43
Firmware (HW/FW) Status, and Maintenance status. In the Diagnostics window, click on Update diagnostics to update diagnostic information and refresh linked icons. Update Open the menu View – Update to refresh the screen. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 39...
Operation via Web Browser (USB) Features The web browser interface in SITRANS LUT400, designed to work with Windows XP , makes monitoring and adjustments easy. Internet Explorer installed on a computer can be used to Abyss configure the SITRANS LUT400, and the Web Server is supplied for your convenience.
Double-click the .exe file to install the web browser. Click Next. Read and accept the Siemens licence agreement, then click Next. Browse to, or accept the default file location (recommended), where the web browser will be installed, then click Next.
To access the device via the web browser, double-click the desktop shortcut SITRANS LUT400, or go to Start > Programs > SITRANS LUT400 HART Browser Interface (created during the installation process). The Abyss server will autostart (if not already running) and the following...
Page 48
Click on Connect to device. The following screen will appear. [SITRANS LUT440 (OCM) device is shown here for example purposes.] Click on Home to update menu, based on your device configuration. Page 44 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
As you enter values on each menu level, click Cancel to abort or Transfer to Device to apply your changes. Configuring a new device To configure the SITRANS LUT400 for a simple application, navigate through the parameter function groups and enter values suited to your application. The Browser menu structure is LCD Menu Structure very similar to the LCD Menu Structure.
• An asterisk (*) in the left column means this parameter or function group will not display on the browser menu unless the SITRANS LUT400 is configured for Pump and Flow* or OCM* at startup, and the device connected supports this functionality.
Page 51
Universal Head vs Flow Totalizers 2.16 AINTENANCE AND IAGNOSTICS Diagnostics Pump Records Temperature Peak Values Echo Quality Maintenance Remaining Device Lifetime Remaining Sensor Lifetime Service Schedule Calibration Schedule Alarms and Device Status A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 47...
Page 52
Parameter Function Group Number OMMUNICATION ECURITY ANGUAGE This menu displays an Alarm Summary and Device Status (list of any detected faults) that would otherwise be displayed on the optional LCD. Page 48 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Operation via AMS Device Manager (HART) (SITRANS LUT400 compatible with AMS version 10.5 and higher) Features AMS Device Manager is a software package used to commission and maintain SITRANS LUT400 and other process devices. Please consult the LUT400 online help, or the manufacturer’...
Italian, Portuguese and Russian are not supported in AMS Device Note: Manager for SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese.
Page 55
Parameter Configuration Charts listing all parameters and available options for each application type are available on our website. Go to: www.siemens.com/sitransLUT400 > Support > Application Guides. You can record data and select from options on the chart that apply to your application, then complete the Quick Start Wizards via AMS Device Manager on page 54.
A pull-down menu under Actions gives alternative access to several features. Scan Device • Open the menu Actions > Scan Device. Scan Device uploads parameters from the device (synchronizes parameters). Page 52 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Open the pull-down menu Actions – Scan Device to synchronize parameters (upload parameters from the device to AMS). Configure the device via the Quick Start wizard appropriate for the application. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 53...
Message, and Date fields can be left blank.) If desired, make changes then click on Next. Step 2 – Application Select the Siemens transducer connected to the device. Select the Application Type (Level, Space, Distance Select the Temperature Source, and if fixed, enter a Fixed Temperature value.
Page 60
Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Configuration via the AMS Device Manager Quick Start Wizard for a Level application is now complete. Page 56 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Message, and Date fields can be left blank.) If desired, make changes then click on Next. Step 2 – Application Select the Siemens transducer connected to the device. Application Type defaults to Volume. Select the Temperature Source, and if fixed, enter a Fixed Temperature value.
Page 62
Click on Next. Step 4– Ranges Change units if desired (in meters by default). Set High and Low Calibration points. Set Response Rate, Volume Units, and Maximum Volume. Click on Next. Page 58 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 63
Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Configuration via AMS Device Manager Quick Start Wizard for a simple Volume application is now complete. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 59...
Message, and Date fields can be left blank.) If desired, make changes then click on Next. Step 2 – Application Select the Siemens transducer connected to the device. The Application Type defaults to Volume. Select the Temperature Source, and if fixed, enter a Fixed Temperature value.
Page 65
Click on Next. Step 4 – Ranges Change units if desired (in meters by default). Set High and Low Calibration points. Set Response Rate, Volume Units, and Maximum Volume. Click on Next. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 61...
Page 66
Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Configuration via AMS Device Manager Quick Start Wizard for a Volume application with a complex vessel shape is now complete. Page 62 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Message, and Date fields can be left blank.) If desired, make changes then click on Next. Step 2 – Application Select the Siemens transducer connected to the device. The Application Type defaults to Flow. Select the Temperature Source, and if fixed, enter a Fixed Temperature value.
Page 68
Select a Method of Flow Calculation, and set Maximum Head, Flowrate Units, Maximum Flow, Flowrate Decimal, and Low Flow Cutoff. Click on Next. If PMD selected is Universal Head Flow, the Characteristic curve appears. Page 64 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 69
Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Configuration via AMS Device Manager Quick Start Wizard for a Flow application is now complete. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 65...
Enable pump control, then assign a relay to each pump. Click on Next. Step 2 – Vessel Regime Select the pump control mode. Set the service ratio for each pump. Click on Next. Page 66 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 71
Step 4 – Summary Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Pump configuration via AMS Device Manager Pump Control Wizard is now complete. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 67...
View current distance measurement, set desired distance for auto sound velocity, and set sound velocity at 20 degrees Celsius. Real Time Clock • Set current date and time Tests • Perform loop-test Page 68 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 73
Set fail-safe value, material level, and LOE timer Current Output • Set current output function, and mA limits and scale values Volume • Allow volume calculation through setup of units, vessel shape and dimensions A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 69...
Page 74
Enable and configure wall cling reduction, pump run-on, pump start delays, and energy savings Totalizers • Configure pumped volume totalizers Alarms Navigate to Configure/Setup > Setup > Alarms for access to: Page 70 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
• To view a previous profile, click the drop-down arrow on the Time field and select the desired profile (note: available only using AMS version 10. 1 ). A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 71...
Italian, Portuguese and Russian are not supported in AMS Device Note: Manager for SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese.
Page 77
View and configure maintenance settings for the sensor Open the window Remaining Sensor Lifetime. After modifying values/units as required, click on Apply to accept the change. Click on Sensor Replaced to reset Remaining Lifetime to 0 hours. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 73...
Page 78
Note: Write Protection is global and can be set via remote software (such as AMS Device Manager), or at the device. Characteristics Navigate to Configure/Setup > Characteristics to view device certificates and approvals. Page 74 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Click on the Device Diagnostics bar at the bottom of the navigation window, for access to: (Device) Status Hardware/Firmware Status Maintenance warnings and alarms can also be viewed and acknowledged from this view, as well as having access to the Echo Profile. A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 75...
A standard user can change their password in AMS Device Manager. A Local or Domain Windows user cannot change their password using AMS Device Manager and must request their network administrator to do so. Page 76 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Select the user type, standard (AMS Device Manager), local or domain user, and login. From the User Manager window you are able to: • add users • edit existing users A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 77...
3.1.1 Long tag 3.1.2 Descriptor 3.1.3 Message 3.1.4 Date 3.1.5 Order Number 3.1.7 Language Step 2 of 4: Application (tab) Transducer 2.1.6 Application Type Temperature Source 2.12.1.3 Fixed Temperature 2.12.1.4 Page 78 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 83
Step 2 of 5: Application (tab) Transducer 2.1.6 Application Type Temperature Source 2.12.1.3 Fixed Temperature 2.12.1.4 Step 3 of 5: Vessel Shape (tab) Vessel Shape 2.6.1 Step 4 of 5: Ranges (tab) Units 2.1.1 A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 79...
Page 84
Message 3.1.4 Date 3.1.5 Order Number 3.1.7 Language Step 2 of 5: Application (tab) Transducer 2.1.6 Application Type Temperature Source 2.12.1.3 Fixed Temperature 2.12.1.4 Step 3 of 5: Shape (tab) Page 80 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 85
Wizard - Quick Start (Flow) Step 1 of 5: Identification (tab) 3.1.1 Long TAG 3.1.2 Descriptor 3.1.3 Message 3.1.4 Date 3.1.5 Order Number 3.1.7 Language Step 2 of 5: Application (tab) A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 81...
Page 86
2.15.3.4 Step 5 of 5: Summary (tab) Long TAG Descriptor Message Date Language Transducer Application Type Temperature Source Fixed Temperature Primary Measuring Device Method of Flow Calculation V-Notch Flow Exponent Page 82 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 87
Step 4 of 4: Summary (tab) Pump Control Enable Relay Pump 1 Relay Pump 2 Pump Control Mode Service Ratio Pump 1 Service Ratio Pump 2 ON Setpoint Pump 1 A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 83...
Long TAG 3.1.2 Master Reset 3.2.3 Configuration Flag Reset Reset Min/Max Temperatures (OCM) Reset Daily Totalizers 2.16.5 (OCM) Reset Running Totalizer 2.16.6 (Pumped Volume) Reset Running Totalizer 2.7.3.5 ETUP Sensor Page 84 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 89
Maximum mA Limit 2.5.6 Volume (tab) Long TAG 3.1.2 Vessel Shape 2.6.1 Volume Units 2.6.2 Maximum Volume 2.6.3 Vessel Dimension A 2.6.4 Vessel Dimension L 2.6.5 User Defined Unit 2.6.6 Linearization A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 85...
Peak 5 End Time 2.7.2.2.12 Peak ON Setpoint Pump 1 2.7.2.2.13 Peak OFF Setpoint Pump 1 2.7.2.2.14 Peak ON Setpoint Pump 2 2.7.2.2.15 Peak OFF Setpoint Pump 2 2.7.2.2.16 Totalizers Page 86 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 91
2.8.6.2 Low Temperature Value Off 2.8.6.3 Assigned Relay 2.8.6.4 Alarm State 2.8.6.5 (High Temperature Alarm) Enable 2.8.7.1 High Temperature Value On 2.8.7.2 High Temperature Value Off 2.8.7.3 Assigned Relay 2.8.7.4 A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 87...
Page 92
(Pump Interlock) Enable Pump 1 2.9.3.1 Pump 1 Discrete Input 2.9.3.2 (Pump Interlock) Enable Pump 2 2.9.3.3 Pump 2 Discrete Input 2.9.3.4 Data Logging (tab) Long TAG 3.1.2 (Process Value Log) Enable 2.10.1.1 Page 88 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 93
Long TAG 3.1.2 Sound Velocity 2.12.1.1 Process Temperature 2.12.1.2 Temperature Source 2.12.1.3 Fixed Temperature 2.12.1.4 Sound Velocity at 20 degrees C 2.12.1.5 Echo Select Echo Select (tab) Long TAG 3.1.2 A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 89...
Page 94
Date and Time Daylight Saving Daylight Saving (tab) Long TAG 3.1.2 Enable 2.14.3. 1 Starting Ordinal 2.14.3.2 Starting Day 2.14.3.3 Starting Month 2.14.3.4 Ending Ordinal 2.14.3.5 Ending Day 2.14.3.6 Ending Month 2.14.3.7 Page 90 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Long TAG 3.1.2 Run Time Relay 2 3.2.7.1 Run Time Relay 3 3.2.7.2 Relay Pump 1 3.2.7.3 Relay Pump 2 3.2.7.4 Set Pumps Runtimes Wear Wear (tab) Long TAG 3.1.2 A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 91...
Page 96
Remaining Sensor Lifetime Remaining Sensor Lifetime (tab) Long TAG 3.1.2 Time Units Lifetime (Expected) 3.3.4.1 Time in Operation 3.3.4.2 Remaining Lifetime 3.3.4.3 Activation of Reminders 3.3.4.4 Reminder 1 before Lifetime 3.3.4.5 (Required) Page 92 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 97
Calibration Performed OMMUNICATION Communication Communication (tab) Long TAG 3.1.2 Manufacturer’s ID Product ID Device Revision EDD Revision Device ID Universal Command Revision Protocol Common Practice Command Revision Cfg chng count A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 93...
Page 98
Acknowledge Warnings 3.3.4.9 (Service Schedule Status listing) Acknowledge Warnings 3.3.5.9 (Calibration Schedule Status listing) Acknowledge Warnings 3.3.6.9 Echo Profile Echo Profile (tab) Long TAG 3.1.2 Measure Level Measurement 2.12.5. 1 Page 94 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 99
2.12.5. 1 Space Measurement 2.12.5.2 Distance Measurement 2.12.5.3 Discrete Inputs and Relays View Discrete Inputs and Relays (tab) Long TAG 3.1.2 Relay 1 Programming Relay 2 Programming Relay 3 Programming A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 95...
Note: Italian, Portuguese and Russian are not supported in Field Communicator FC375/ 475 for SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese.
HART FC375/FC475 Menu Structure Notes: • HART Communicator 375/475 is supported by SITRANS LUT400 HART. The menu structure is aligned with the menu structure for AMS Device Manager. • For date fields, the format for HART FC375/FC475 is MM-DD-YYYY. SITRANS LUT400...
Page 103
6 ================ 7 Step 3 of 4: Pump Setpoints 1 ON Setpoint Pump 1 2 OFF Setpoint Pump 1 3 ON Setpoint Pump 2 4 OFF Setpoint Pump 2 6 ================== A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 99...
Page 104
Configuration Flag Reset 1 Yes 2 No 4 Setup 1 Sensor 1 Units 2 Sensor Mode 3 Sensor Mode Seco... 4 Transducer 5 Frequency 6 Long Shot Duration 7 Short Shot Duration Page 100 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 105
7 ON Setpoint Pump 2 8 OFF Setpoint Pump 2 9 Serv Ratio Pump 1 Serv Ratio Pump 2 2 Modifiers 1 Wall Cling Reduction 1 Enable 2 Level Setpoint Vari... A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 101...
Page 106
3 Low Level Value 4 Assigned Relay 5 Alarm State 3 Low Level Alarm 1 Enable 2 Low Level Value On 3 Low Level Value Off 4 Assigned Relay 5 Alarm State Page 102 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 108
5 Assigned Relay 6 Relay Logic Signal Processing 1 Temperature and Velocity 1 Sound Velocity 2 Process Temperature 3 Temperature Source 4 Fixed Temperature 5 Sound Veloc at 20 C Page 104 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 109
1 OCM Flow Totalizers 1 Daily Total High 2 Daily Total Low 3 Running Total High 4 Running Total Low 5 Totalizer Dec. Pos. 6 Totalizer Multiplier 7 Low Flow Cutoff A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 105...
Page 119
5 Assigned Relay 6 Relay Logic Signal Processing 1 Temperature and Velocity 1 Sound Velocity 2 Process Temperature 3 Temperature Source 4 Fixed Temperature 5 Sound Veloc at 20 C A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 115...
Page 120
1 OCM Flow Totalizers 1 Daily Total High 2 Daily Total Low 3 Running Total High 4 Running Total Low 5 Totalizer Dec. Pos. 6 Totalizer Multiplier 7 Low Flow Cutoff Page 116 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 121
2 Lifetime (Expected) 3 Time in Operation 4 Remaining Lifetime 5 Activation of Remi... 6 Sensor Remind 1 7 Sensor Remind 2 8 Sensor Replaced 9 Snooze for 1 year A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 117...
Page 122
<Device status listing> 2 HW/FW-Status <HW/FW-Status listing> 3 Maintenance 1 Device Lifetime 1 Status 2 Ack Status 3 Ack Warnings 2 Sensor Lifetime 1 Status 2 Ack Status 3 Ack Warnings Page 118 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 123
6 Relay 3 Activated 2 Discrete Input Programmed State 1 DI 1 Programmed 2 DI 2 Programmed 3 DI 1 Scaled State 4 DI 2 Scaled State 5 SITRANS LUT400 <Device Image> A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 119...
Page 124
4 <calculation factor based on PMD> 5 <calculation factor based on PMD> 6 <calculation factor based on PMD> 7 <calculation factor based on PMD> 8 <calculation factor based on PMD> Page 120 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 125
OCM Dimension 3 OCM Dimension 4 -------------------- Units Low Calib. Pt. High Calib. Pt. Response Rate Maximum Head Flowrate Units Flowrate Decimal Low Flow Cutoff Maximum Flow at 2.. --------------------- A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 121...
Page 126
1 Select Analog Output 2 Auto Zero Head 1 Zero Head Offset 2 Head 3 Actual Head Value 3 Auto Sensor Offset 1 Sensor Offset 2 Distance 3 Desired Distance fo... Page 122 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 127
4 Minimum mA Limit 5 Maximum mA Limit 6 Volume 1 Vessel Shape 2 Volume Units 3 Maximum Volume 4 Vessel Dimension A 5 Vessel Dimension L 6 User Defined Unit A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 123...
Page 128
1 Pump Start Delay 2 Power Resumption Del... 3 Totalizers 1 Running Total High 2 Running Total Low 3 Totalizer Dec. Pos. 3 Totalizer Multiplier 4 Inflow/Disch. Adj. 8 Alarms 1 Level Page 124 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 129
3 Alarm State 5 Relay Logic 1 Relay 1 Logic 2 Relay 2 Logic 3 Relay 3 Logic 6 Time to Spill 1 Level to Spill 2 Minutes Left to Spill A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 125...
Page 130
2 Interval 3 Relay Duration 4 Assigned Relay 5 Relay Logic 2 Time of Day Relay 1 Enable 2 Activation Time 3 Relay Duration 4 Assigned Relay 5 Relay Logic Page 126 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 131
Date and Time 1 Daylight Saving 1 Enable 2 Starting Ordinal 3 Starting Day 4 Starting Month 5 Ending Ordinal 6 Ending Day 7 Ending Month Flow 1 OCM PMD A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 127...
Page 132
1 Run Time Relay 2 2 Run Time Relay 3 3 Relay Pump 1 4 Relay Pump 2 5 Set Pumps Runtimes 2 Wear 1 Power-on TIme 2 Power-on Resets Page 128 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 133
5 Calibration Schedule 1 Time Units 2 Calibration Interval 3 Since Last Calibrat... 4 Until Next Calibrat... 5 Activation of Remi... 6 Cal. Remind 1 7 Cal. Remind 2. 8 Cal. Performed A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 129...
Page 134
4 Calibration Schedule 1 Status 2 Ack Status 3 Ack Warnings 4 Echo Profile 1 Echo Profile 2 Level 3 Distance 4 Near Range 5 Confidence 6 Echo Strength 7 Algorithm Page 130 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270...
Page 135
6 Relay 3 Activated 2 Discrete Input Programmed State 1 DI 1 Programmed 2 DI 2 Programmed 3 DI 1 Scaled State 4 DI 2 Scaled State 5 SITRANS LUT400 <Device Image> A5E33701270 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL Page 131...
Support and click on Application Guides. Note: Italian, Portuguese and Russian are not supported in SITRANS DTM for SITRANS LUT400. If the device is set to one of these languages, it may be necessary to switch the device to English, German, French, Spanish or Chinese.