hit counter script

Siemens SITRANS LUT400 Manual page 25

Communications (hart)
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

Step 4 - Ranges
1)
Modify parameters as required.
2.
If PMD selected in Step 3 was Universal Head Flow, the Linearization button will
appear in Step 4. Click on Linearization to set Head and Flow Breakpoints, then click
OK to return to the Step 4.
3.
Click on Next.
Notes:
• If entering or modifying breakpoints via the parameter menu (after initial wizard
is complete), ensure
Head Flow prior to head/flow values being transferred, otherwise two uploads
must be performed:
Step 5 – Summary
1.
Check parameter settings, and click on Cancel to abort, or apply your changes.
2.
Click Apply to save your changes and return to the main menu, or click Apply and
Transfer to save your changes and transfer settings to the device.
The message Quick Setup was successful will appear. Click on OK.
Configuration via SIMATIC PDM Quick Start Wizard for a Flow application is now
complete.
A5E33701270
COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL
2.15.1.Primary Measuring Device (PMD)
a) one to read Universal Head Flow as enabled,
b) and one to transfer breakpoint values.
is set to Universal
Page 21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents