Parameter reference (LUI)
9.3 Maintenance and Diagnostics (3.)
Lifetime Expected (3.3.3.1.)
Note
The device always operates in years. Changing the Time Units affects only the parameter
view of the Remaining Device Lifetime parameters in SIMATIC PDM, PACTware FDT, and AMS.
Allows you to override the factory default.
Values
Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS.
1)
Time in Operation (3.3.3.2.)
Read only. The amount of time the device has been operating.
Remaining Lifetime (3.3.3.3.)
Read only. Lifetime Expected (3.3.3.1.) (Page 252) less Time in Operation (3.3.3.2.)
(Page 252).
Reminder Activation (3.3.3.4.)
Note
To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu
Device – Maintenance.
Allows you to enable a maintenance reminder.
Options
1. First set the values in Reminder 1 before Lifetime (Required) (3.3.3.5.) (Page 253)/Reminder
2 before Lifetime (Demanded) (3.3.3.6.) (Page 253).
2. Select the desired Reminder Activation option.
252
Units
: hours, days, years
1
Range: 0.000 to 20.000 years
Default: 10.000 years
REMINDER 1 (MAINTENANCE REQUIRED)
REMINDER 2 (MAINTENANCE DEMANDED)
REMINDERS 1 AND 2
*
OFF
Operating Instructions, 04/2021, A5E33329501-AG
SITRANS LUT400