hit counter script

Information List; Oscillographic Fault Records; Description - Siemens 7SK80 Manual

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Functions
2.1 General
Addr.
Parameter
614A
OP. QUANTITY 59
615A
OP. QUANTITY 27

2.1.3.4 Information List

No.
Information
5145
>Reverse Rot.
5147
Rotation ABC
5148
Rotation ACB
10036
Capac.Par.Fail.
2.1.4

Oscillographic Fault Records

The Multifunctional Protection with Control 7SK80 is equipped with a fault record memory. The instantaneous
values of the measured values
i
, i
, i
, i
, i
A
B
C
N
Ns
(voltages depending on connection) are sampled at intervals of 1.0 ms (at 50 Hz) and stored in a revolving
buffer (20 samples per cycle). In the event of a fault, the data are recorded for a set period of time, but not for
more than 5 seconds. A minimum of 8 faults can be recorded in this buffer. The fault record memory is auto-
matically updated with every new fault, so no acknowledgment for previously recorded faults is required. In ad-
dition to protection pickup, the recording of the fault data can also be started via a binary input or via the serial
interface.

2.1.4.1 Description

The data of a fault event can be read out via the device interface and evaluated with the help of the SIGRA 4
graphic analysis software. SIGRA 4 graphically represents the data recorded during the fault event and also
calculates additional information from the measured values. Currents and voltages can be presented either as
primary or as secondary values. Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
If port B of the device has been configured correspondingly, the fault record data can be imported by a central
controller via this interface and evaluated. Currents and voltages are prepared for a graphic representation.
Signals are additionally recorded as binary tracks (marks), e.g. "pickup", "trip".
The retrieval of the fault data by the central controller takes place automatically either after each protection
pickup or after a tipping.
If device parameter 651 ParEN100(LC)blk is set to ON, you can also read out fault records via port A (see
Section 2.1.2.2).
52
C
Setting Options
Vphph
Vph-n
V1
V2
V1
Vphph
Vph-n
Type of In-
formation
SP
OUT
OUT
OUT
and v
, v
, v
, v
, v
, v
A
B
C
AB
BC
CA
Default Setting
Vphph
V1
>Reverse Phase Rotation
Phase rotation ABC
Phase rotation ACB
Malparameteriz. Volt.-divider Capacities
, v
, v
N
X
E50417-G1140-C344-A5, Release date 11.2012
Comments
Opera. Quantity for 59 Ov-
ervolt. Prot.
Opera. Quantity for 27 Un-
dervolt. Prot.
Comments
SIPROTEC, 7SK80, Manual

Advertisement

Table of Contents
loading

Table of Contents