2.20.5.2 Setting Notes

Minimum and Maximum Values
The tracking of minimum and maximum values can be reset automatically at a programmable point in time. To
select this feature, address 8311 MinMax cycRESET should be set to YES. The point in time when reset is to
take place (the minute of the day in which reset will take place) is set at address 8312 MiMa RESET TIME.
The reset cycle in days is entered at address 8313 MiMa RESETCYCLE, and the beginning date of the cyclical
process, from the time of the setting procedure (in days), is entered at address 8314 MinMaxRES.START.

2.20.5.3 Settings

Addr.
Parameter
8311
MinMax cycRESET
8312
MiMa RESET TIME
8313
MiMa RESETCYCLE
8314
MinMaxRES.START

2.20.5.4 Information List

No.
Information
-
ResMinMax
395
>I MinMax Reset
396
>I1 MiMaReset
397
>V MiMaReset
398
>VphphMiMaRes
399
>V1 MiMa Reset
400
>P MiMa Reset
401
>S MiMa Reset
402
>Q MiMa Reset
403
>Idmd MiMaReset
404
>Pdmd MiMaReset
405
>Qdmd MiMaReset
406
>Sdmd MiMaReset
407
>Frq MiMa Reset
408
>PF MiMaReset
> Θ MiMa Reset
412
837
IAdmdMin
838
IAdmdMax
839
IBdmdMin
840
IBdmdMax
841
ICdmdMin
842
ICdmdMax
843
I1dmdMin
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
Setting Options
NO
YES
0 .. 1439 min
1 .. 365 Days
1 .. 365 Days
Type of In-
formation
IntSP_Ev
Reset Minimum and Maximum counter
SP
>I MIN/MAX Buffer Reset
SP
>I1 MIN/MAX Buffer Reset
SP
>V MIN/MAX Buffer Reset
SP
>Vphph MIN/MAX Buffer Reset
SP
>V1 MIN/MAX Buffer Reset
SP
>P MIN/MAX Buffer Reset
SP
>S MIN/MAX Buffer Reset
SP
>Q MIN/MAX Buffer Reset
SP
>Idmd MIN/MAX Buffer Reset
SP
>Pdmd MIN/MAX Buffer Reset
SP
>Qdmd MIN/MAX Buffer Reset
SP
>Sdmd MIN/MAX Buffer Reset
SP
>Frq. MIN/MAX Buffer Reset
SP
>Power Factor MIN/MAX Buffer Reset
SP
>Theta MIN/MAX Buffer Reset
MVT
I A Demand Minimum
MVT
I A Demand Maximum
MVT
I B Demand Minimum
MVT
I B Demand Maximum
MVT
I C Demand Minimum
MVT
I C Demand Maximum
MVT
I1 (positive sequence) Demand Minimum
Default Setting
YES
Automatic Cyclic Reset Function
0 min
MinMax Reset Timer
7 Days
MinMax Reset Cycle Period
1 Days
MinMax Start Reset Cycle in
Comments
Functions
2.20 Auxiliary Functions
Comments
279