hit counter script

Settings; Information List - Siemens 7SK80 Manual

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

2.6.4

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
4001
FCT 46
4002
46-1 PICKUP
4003
46-1 DELAY
4004
46-2 PICKUP
4005
46-2 DELAY
4006
46 IEC CURVE
4007
46 ANSI CURVE
4008
46-TOC PICKUP
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A
46 T DROP-OUT
2.6.5

Information List

No.
Information
5143
>BLOCK 46
5151
46 OFF
5152
46 BLOCKED
5153
46 ACTIVE
5159
46-2 picked up
5165
46-1 picked up
5166
46-TOC pickedup
5170
46 TRIP
5171
46 Dsk pickedup
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
C
Setting Options
OFF
ON
1A
0.05 .. 3.00 A
5A
0.25 .. 15.00 A
0.00 .. 60.00 sec; ∞
1A
0.05 .. 3.00 A
5A
0.25 .. 15.00 A
0.00 .. 60.00 sec; ∞
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
1A
0.05 .. 2.00 A
5A
0.25 .. 10.00 A
0.50 .. 15.00 ; ∞
0.05 .. 3.20 sec; ∞
Instantaneous
Disk Emulation
0.00 .. 60.00 sec
Type of In-
formation
SP
>BLOCK 46
OUT
46 switched OFF
OUT
46 is BLOCKED
OUT
46 is ACTIVE
OUT
46-2 picked up
OUT
46-1 picked up
OUT
46-TOC picked up
OUT
46 TRIP
OUT
46 Disk emulation picked up
2.6 Negative Sequence Protection 46
Default Setting
OFF
46 Negative Sequence
Protection
0.10 A
46-1 Pickup
0.50 A
1.50 sec
46-1 Time Delay
0.50 A
46-2 Pickup
2.50 A
1.50 sec
46-2 Time Delay
Extremely Inv.
IEC Curve
Extremely Inv.
ANSI Curve
0.90 A
46-TOC Pickup
4.50 A
5.00
46-TOC Time Dial
0.50 sec
46-TOC Time Dial
Instantaneous
46-TOC Drop Out
0.00 sec
46 Drop-Out Time Delay
Comments
Functions
Comments
127

Advertisement

Table of Contents
loading

Table of Contents