2.20.8

Energy Metering

Metered values for active and reactive energy are determined by the device. They can be output via the display
of the device, read out with DIGSI via the operator interface or transmitted to a control center via port B.

2.20.8.1 Description

Metered Values for Active and Reactive Energy
Metered values of the real power W
hours primary or in kVARh, MVARh or GVARh primary, separately according to the input (+) and output (–), or
capacitive and inductive. The measured-value resolution can be configured. The signs of the measured values
appear as configured in address 1108 P,Q sign (see Section „Display of Measured Values").

2.20.8.2 Setting Notes

Setting of parameter for meter resolution
Parameter 8315 MeterResolution allows increasing the resolution of the energy metered values by the
Factor 10 or Factor 100 compared to the Standard setting.

2.20.8.3 Settings

Addr.
Parameter
8315
MeterResolution

2.20.8.4 Information List

No.
Information
-
Meter res
888
Wp(puls)
889
Wq(puls)
916
WpΔ=
917
WqΔ=
924
WpForward
925
WqForward
928
WpReverse
929
WqReverse
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
and reactive power (W
p
Setting Options
Standard
Factor 10
Factor 100
Type of In-
formation
IntSP_Ev
Reset meter
PMV
Pulsed Energy Wp (active)
PMV
Pulsed Energy Wq (reactive)
-
Increment of active energy
-
Increment of reactive energy
MVMV
Wp Forward
MVMV
Wq Forward
MVMV
Wp Reverse
MVMV
Wq Reverse
) are acquired in kilowatt, megawatt or gigawatt
q
Default Setting
Standard
Meter resolution
Comments
Functions
2.20 Auxiliary Functions
Comments
283