3.1.2.5 Interface Modules

General
The 7SK80 relay is supplied with preconfigured interfaces according to the ordering version. You do not have
to make any adaptations to the hardware (e.g. plugging in jumpers) yourself, except for the installation or re-
placement of communication modules.
The use of the interface modules RS232, RS485 and optical can be defined via the parameter 617 ServiProt.
This parameter is only visible if the 11th digit of the ordering number was selected to be 1 for RS232, 2 for
RS485 or 3 for optical.
Installation or Replacement of the Ethernet Interface Module
The following requirement must be fulfilled:
There is no SIPROTEC 4 communication module mounted yet. Otherwise, this has to be removed before ac-
tually installing the Ethernet interface module (see below).
The Ethernet interface module is inserted in the respective slot, most suitably from the open bottom, i.e. above
the back of the battery case. A supporting frame is placed over the modular plug. The narrow spacer lies at
edge of the printed circuit board. The module is attached to the 50-pole plug connector of the CPU module
slightly inclined to the basic I/O board. The supporting plate is slightly pulled outwards in this area. The module
can now be inserted vertically up to the stop. Then, the supporting plate is pressed against in the area of the
locking latch until the upper edge of the printed circuit board of the Ethernet interface module snaps into the
locking latch.
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
Terminal block "D" with cover
Mounting and Commissioning
3.1 Mounting and Connections