hit counter script

Final Preparation Of The Device - Siemens 7SK80 Manual

Siprotec motor protection
Hide thumbs Also See for 7SK80:
Table of Contents

Advertisement

Mounting and Commissioning

3.4 Final Preparation of the Device

3.4
Final Preparation of the Device
Firmly tighten all screws. Tighten all terminal screws, including those that are not used.
Caution!
Inadmissable Tightening Torques
Non–observance of the following measure can result in minor personal injury or property damage.
The tightening torques must not be exceeded as the threads and terminal chambers may otherwise be dam-
aged!
The settings should be checked again, if they were changed during the tests. Check if all protection, control
and auxiliary functions to be found with the configuration parameters are set correctly (Section 2.1.1, Functional
Scope) and all desired functions are set to ON. Keep a copy of all setting values on a PC.
The device-internal clock should be checked and set, if necessary.
The annunciation buffers are deleted under MAIN MENU → Annunciations → Set/Reset, so that future infor-
mation will only apply to actual events and states (see also SIPROTEC 4 System Description). The counters
in the switching statistics should be reset to the values that were existing prior to the testing (see also
SIPROTEC 4 System Description).
Reset the counter of the operational measured values (e.g. operation counter, if available) under MAIN MENU
→ Measured Values → Reset (also see SIPROTEC 4 System Description).
Press the E
SC
the display box (e.g. the display of operational measured values).
Clear the LEDs on the front panel of the device by pressing the L
and states in the future. In this context, also output relays probably memorized are reset. While pressing the
L
ED
key, the allocatable LEDs on the front panel light up, therefore this also serves as an LED test. LEDs indi-
cating current conditions remain on, of course.
For more information on the operation, see 2.22 and the SIPROTEC 4 System Description.
The green „RUN" LED must light up, whereas the red „ERROR" must not light up.
Close the protective switches. If test switches are available, then these must be in the operating position.
The device is now ready for operation.
348
key (several times if necessary), to return to the default display. The default display appears in
ED
key so that they will show only real events
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012

Advertisement

Table of Contents
loading

Table of Contents