4.3

Commissioning with factory settings

Prerequisites for using the factory settings
In simple applications, commissioning can be carried out just using the factory settings.
Check which factory settings can be used and which functions need to be changed. During
this check you will probably find that the factory settings only require slight adjustment:
1. The inverter and motor must match one another; compare the data on the motor rating
2. If you are controlling the drive using the digital and analog inputs, the inverter must be
3. If you connect the drive to a fieldbus, you must set the bus address using the DIP
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
plate with the technical data of the Power Module.
– The rated inverter current must, as a minimum, be the same as the motor.
– The motor power should match that of the inverter; motors can be operated in the
power range from 25 % ... 100 % of the inverter power rating.
connected as shown in the wiring example. (see Wiring examples for the factory settings
(Page 64) )
switches on the front of the Control Unit.
4.3 Commissioning with factory settings
Commissioning
63