4.6.3
Saving settings and transferring them using an operator panel
You start the download or upload in the "TOOLS" menu.
Download for inverters with enabled safety functions
You must confirm the settings of the safety functions.
Table 4- 4
Set the following parameters
p9761 = ...
p0010 = 95
p9701 = 220
p0010 = 0
Final steps:
1. Switch off the inverter supply voltage
2. Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
4.6.4
Other ways to back up settings
You can backup three additional settings of the parameters in memory areas of the inverter
reserved for this purpose. You will find additional information in the List Manual under the
following parameters:
Parameter
p0970
p0971
You can back-up up to 99 additional parameter settings on the memory card. You will find
additional information in the List Manual under the following parameters:
Parameter
p0802
p0803
p0804
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Procedure
Password for the safety functions
Changing the safety functions
Confirm the settings of the safety functions
Exit change
again. Your settings only become effective after this power-on reset.
Description
Resetting drive parameters
Load the back-up setting (number 10, 11 or 12). You overwrite your actual parameter
setting when loading.
Saving parameters
Backing up the setting (10, 11 or 12).
Description
Data transfer with memory card as source/target
Data transfer with device memory as source/target
Start data transfer
4.6 Data backup and standard commissioning
Commissioning