Indicators
ECS touchscreen and EPO indicators
The ECS touchscreen and EPO indicators are located on the door to the control panel.
The touchscreen enables you to easily configure the environmental parameters, access data, and monitor
environmental, life safety, and access control conditions within the HP POD 20c.
The EPO indicators provide EPO status. The EPO key control and EPO reset button enable you to adjust the
EPO system mode.
Item Component
Power on indicator
1
EPO shutdown indicator
2
EPO armed indicator
3
EPO test mode indicator
4
EPO bypassed indicator
5
EPO mode key control
6
EPO reset button
7
EPO horn
8
Indicator Color
Description
White
Indicates the EPO power status
Red
Indicates an EPO shutdown or alarm
situation
White
Indicates that the EPO system is armed and
operational
Yellow
Indicates that the EPO system is operating
in test mode or that an EPO cover is open
Green
Indicates that the EPO shut down
functionality is bypassed
—
Enables you to select the EPO mode.
—
Resets the EPO system when pressed
—
Sounds when an EPO event occurs.
Removal and replacement procedures 30