4.6 Installing Control Unit
4.6.4.1

Factory setting of the CU240E-2 interfaces

Factory setting of the terminal strip on the CU240E-2
The factory setting of the terminal strip depends on the Control Unit.
Control Units with USS interface
The fieldbus interface is not active.
--- No function.
DO x: p073x
Speed setpoint (main setpoint): p1070[0] = 755[0]
Image 4-14
Factory setting of the CU240E-2 and CU240E-2 F Control Units
102
AO 0: p0771[0]
DI x: r0722.x
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
AI 0: r0755[0]