Number / Alarm
Cause
A082
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
No valid PPO type can be identified from the
configuration telegram of the DP master.
Consequence:
No connection is made with the PROFIBUS
master.
A083
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
No net data or invalid net data (e.g. complete
control word STW1=0) are being received
from the DP master.
Consequence:
The process data are not passed on to the
dual port RAM. If P722 (P695) is not equal to
zero, this will cause the fault message F082 to
be tripped.
A084
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
The telegram traffic between the DP master
and the CBP has been interrupted (e.g. cable
break, bus cable pulled out or DP master
powered down).
Consequence:
If P722 (P695) is not equal to zero, this will
cause the fault message F082 to be tripped.
A085
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
The CBP does not generate this alarm!
A086
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
Failure of the heartbeat counter on the basic
unit. The heartbeat counter on the basic unit is
no longer being incremented. The
communication between the CBP and the
basic board is disturbed.
A087
The following description refers to the 1st
CBP. For other CBs or the TB see the
CB alarm
operating instructions for the CB board.
Fault in the DPS manager software of the
CBP.
A088
See user manual for CB board
CB alarm
A089
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A81 of the 1st CB board
A090
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A82 of the 1st CB board
A091
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A83 of the 1st CB board
A092
See user manual for CB board
Alarm of the 2nd CB board corresponds to
CB alarm
A84 of the 1st CB board
Siemens AG
6SE7087-2JK50
SIMOVERT MASTERDRIVES
Operating Instructions
Counter-measure
New configuration necessary.
See operating instructions of the CB board
See operating instructions of the CB board
See operating instructions of the CB board
See operating instructions of the CB board
See operating instructions of the CB board
See user manual for CB board
See user manual for CB board
See user manual for CB board
See user manual for CB board
See user manual for CB board