8.1.7

Configuring operating sources

• Assign the functions mentioned above to the desired operating source.
– You can configure operating sources for Local using internal display, Remote, using
• Using command Op.-source in menu P- INTERFACE:Op.-source, set your preselection for
the on-off commands.
• If you wish to toggle between Local and Remote, then initiate the switchover using a
completed configuration under P-OPERATION:Opr. or change the setting P-PARAMETER
SWITCH.
• Select the reset source for the reset command under P-INTERFACE.
– If you would like to activate the reset independently of the operating source
8.1.8

Invoking mode configurations

Call the completed operating configuration under P-OPERATION:Opr.. Settings for the
controls and the parameter switches are automatically made in these configurations.
For each selection, there is an associated connection plan and a specified mode of
functioning of the display buttons and digital inputs. You can find additional details in
Chapter "Standard mode settings (Page 87)".
Changes in the menu P-OPERATION cause under P-OPERATION:Opr. the addition spec. as
information that something has been changed from the standard.
Installation and Operating Instructions for LOHER DYNAVERT I Series 7
Operating Instructions, 10/2022, 4BS0745-002
control cable terminal strip -X2 and Bus.
changeover, then set Global. The reset is then possible at all operating sources.
Operation
8.1 Operation
83