Operation
10.5 Performing a reset
Error message
Process image error (both relay switching options
are selected simultaneously via IO-Link)
Preset <> Actual Configuration
"Non-acknowledgeable faults"
In manual mode only (control via operator panel).
1)
In automatic mode only (control via IO-Link).
2)
Fault acknowledgment and resetting of the relay switching states only by opening and reclosing the
3)
3RB24 overload relay.
10.5.1
Manual reset
Manual reset
If the slide switch on the device is set to "MAN", you can acknowledge faults in the following
ways:
• Trip reset (process image of the outputs via IO-Link)
• TEST/RESET button on the 3RB24 overload relay
• SF/RESET button on the 3RA6935-0A operator panel
• Remote reset: Remote reset can be implemented electrically by jumpering terminals Y1
and Y2.
Automatic restart!
Can result in death, serious injury, or property damage.
The motor switches on again when the following condition is met:
• the overload relay is in automatic mode, and following the reset, the pending control
Manual reset must not be used in applications where there is a risk of serious injury to persons
or substantial damage to property if the motor starts up again unexpectedly.
Make sure that the machine danger zone is kept clear of people at the time of restarting.
92
WARNING
commands DO 0.0 / DO 0.1 of the higher-level controller are executed again.
Manual reset
✓
2)
✓
—
3)
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003
Automatic reset
✓
✓
—
3)