6.9 Operation with operator panel

6.9
Operation with operator panel
6.9.1

"Operator panel available" parameter

With the "Operator panel available" parameter, you determine whether or not an operator panel
is available for operating the solid-state overload relay.
In conjunction with the "Operation at Preset <> Actual Configuration" parameter, operation of
the solid-state overload relay with or without operator panel can be configured (see Chapter
"Parameter "Operation at Preset <> Actual Operation" (Page 58)").
Use of the operator panel is above all useful if manual intervention in an application is an
indispensable requirement for operating the plant, or to enable manual intervention in an
emergency.
The table below shows the values for the "Operator panel available" parameter.
Table 6-3
Value
0
1
The "Operator panel available" parameter can only be modified via IO‑Link. It cannot be adjusted
at the device.
6.9.2
Parameter "Operation at Preset <> Actual Operation"
The "Operation at Preset <> Actual Configuration" parameter sets the severity level of the test for
the "Operator panel available" parameter.
The table below shows the values for the "Operation at Preset <> Actual Configuration"
parameter.
Table 6-4
Value
0
1
If the value of the "Operation at Preset <> Actual Configuration" parameter is set to "Enable", the
solid-state overload relay can be operated via IO‑Link regardless of whether an operator panel
is connected or not.
If the value of the "Operation at Preset <> Actual Configuration" parameter is set to "Disable", the
solid-state overload relay can only be operated if the setting of the "Operator panel available"
58
"Operator panel available" parameter
Description
Operator panel available: No
Operator panel available: Yes
"Operation at Preset <> Actual Configuration" parameter
Description
Operation at Preset <> Actual Configura‐
tion: Disable
Operation at Preset <> Actual Configura‐
tion: Enable
Default setting
Yes
Default setting
Enable
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003