Parameters - Siemens SIRIUS 3RB24 Manual

Protection devices electronic overload relay
Hide thumbs Also See for SIRIUS 3RB24:
Table of Contents

Advertisement

Parameters

6.1
Parameters
Parameters
You can set the following parameters:
via IO-Link
Notes on parameter assignment
Parameter assignment is carried out in two ways.
With the help of the local control elements, the following parameters can be set:
• Rated operational current I
• Trip class [CLASS] (rotary switch)
• Response to overload - thermal motor model (slide switch for AUTO/MAN-RESET)
• Response to overload - thermistor (slide switch for AUTO/MAN-RESET)
• Thermistor - monitoring (TEST/RESET pushbutton)
The following parameters can be read out via IO‑Link:
• Rated operational current I
• Trip class [CLASS]
• Response to overload - thermal motor model
• Response to overload - thermistor
• Thermistor - monitoring
• Cold start
• Ground fault detection
• Operator panel available
• Operation at Preset <> Actual Configuration
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003
Cold start
Ground fault detection
Operator panel available
Operation at Preset <> Actual Configuration
on the device
Rated operational current I
Trip class [CLASS]
Response to overload - thermal motor model
Response to overload - thermistor
Thermistor - monitoring
(rotary switch)
e
[A]
e
6
e
49