1.2
List of Parameters
Product: G120, Version: 3005200, Language: eng
r0000
Drive display / Drive display
Access level: 1
Unit: -
Description:
Displays the user selected output. This value is defined in P0005.
Note:
Pressing the "Fn" button on OP for 2 seconds allows the user to view the values of DC link voltage, output fre-
quency, output voltage, output current, and chosen r0000 setting (defined in P0005).
r0002
Drive state / Drive state
CU240E
Access level: 2
CU240S DP-F
Unit: -
Description:
Displays actual drive state.
Values:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
Dependency:
State 3 visible only while precharging DC link.
It is only visible when an externally powered control unit is fitted.
r0002
Drive state / Drive state
CU240S
Access level: 2
CU240S DP
Unit: -
CU240S PN
Description:
Displays actual drive state.
Values:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
Dependency:
State 3 visible only while precharging DC link.
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Commissioning mode (P0010 != 0)
Drive ready
Drive fault active
Drive starting (DC-link precharging)
Drive running
Stopping (ramping down)
Drive inhibited
Safety active
Safety reset/commissioning
Safety fault active
Commissioning mode (P0010 != 0)
Drive ready
Drive fault active
Drive starting (DC-link precharging)
Drive running
Stopping (ramping down)
Drive inhibited
Safety active
Safety reset/commissioning
Safety fault active
P-Group: -
P-Group: Commands
P-Group: Commands
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Data type: Unsigned16
Data set: -
Data type: Unsigned16
Data set: -
1-13