3.6
Motors and multi-motor drives that can be operated
Siemens motors that can be operated
You can connect standard induction motors to the inverter.
You can find information on further motors on the Internet:
Motors that can be operated
100426622)
Third-party motors that can be operated
You can operate standard asynchronous motors from other manufacturers with the inverter:
NOTICE
Motor damage due to the use of an unsuitable third-party motor
A higher load occurs on the motor insulation in inverter mode than with mains operation.
Damage to the motor winding may occur as a result.
● Please observed the notes in the System Manual "Requirements for third-party motors"
Additional information is provided on the Internet:
Requirements for third-party motors
79690594)
Multi-motor drive
A multi-motor drive involves simultaneously operating several motors from one inverter. For
standard induction motors, multi-motor drives are permissible in installations that are compliant
with IEC.
Further information is provided in the Internet:
Multi-motor drive (http://support.automation.siemens.com/WW/view/en/84049346)
Multi-motor drives are not permissible for installations that are compliant with UL.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
3.6 Motors and multi-motor drives that can be operated
(https://support.industry.siemens.com/cs/ww/en/view/
(https://support.industry.siemens.com/cs/ww/en/view/
Description
49