Installing
4.5 Installing Control Unit
4.5.8
Default settings of the CU240E-2 interfaces
The function of the terminals and fieldbus interface can be set.
In order that you do not have to successively change terminal for terminal, several terminals
can be jointly set using default settings ("p0015 Macro drive unit").
The terminal settings made in the factory described above correspond to the following default
settings:
● Default setting 12 (p0015 = 12): "Standard I/O with analog setpoint"
● Default setting 7 (p0015 = 7): "Fieldbus with data set switchover"
Default setting 1: "Conveyor technology with 2 fixed frequencies"
DO 0: p0730, DO 1: p0731
Fixed speed setpoint 3: p1003, fixed speed setpoint 4: p1004, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
DI 4 and DI 5 = high: The inverter adds both fixed speed setpoints
Designation in the BOP-2: coN 2 SP
Default setting 2: "Conveyor systems with Basic Safety"
DO 0: p0730, DO 1: p0731
Fixed speed setpoint 1: p1001, fixed speed setpoint 2: p1002, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
DI 0 and DI 1 = high: The inverter adds both fixed speed setpoints.
Designation in the BOP-2: coN SAFE
106
AO 0: p0771[0], AO 1: p0771[1]
AO 0: p0771[0], AO 1: p0771[1]
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
DI 0: r0722.0, ..., DI 5: r0722.5
DI 0: r0722.0, ..., DI 5: r0722.5