What Do You Have To Set For Communication Via Profibus - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.6 Connecting the inverter to the fieldbus
4.6.2.2

What do you have to set for communication via PROFIBUS?

Configuring PROFIBUS communication
Proceed as follows to configure the communication between the PROFIBUS master and the
inverter as PROFIBUS slave:
1. Configure the PROFIBUS master and the PROFIBUS slave with an engineering system,
e.g. with HW-Config.
If required, install the GSD file of the inverter in the engineering system.
2. Load the configuration data into the PROFIBUS master.
Setting the address
Set the address of the PROFIBUS slave.
Setting the telegram
Set the telegram in the inverter as in the PROFIBUS master. Interconnect the telegrams in the
control program of the PROFIBUS master with the signals of your choosing.
Application examples
You can find application examples for PROFIBUS communication on the Internet:
Controlling the speed of a SINAMICS G120/S120 with S7-300/400 via PROFINET
support.industry.siemens.com/cs/ww/en/view/38844967)
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
PROFINET, with Safety Integrated (via terminal) and HMI
support.industry.siemens.com/cs/ww/en/view/60441457)
Controlling the speed of a SINAMICS G110M/G120 (Startdrive) with S7-1500 (TO) via
PROFINET, with Safety Integrated (via terminal) and HMI
support.industry.siemens.com/cs/ww/en/view/78788716)
Communication with the controller even when the supply voltage on the Power Module is
switched off
You must supply the Control Unit with 24 V DC at terminals 31 and 32 if you wish to maintain
communication with the control system when the line voltage is switched off.
In the case of brief interruptions of the 24 V power supply, the inverter may signal a fault without
communications with the control system being interrupted.
126
Installing the GSD (Page 127)
Setting the address (Page 127)
Drive control via PROFIBUS or PROFINET (Page 196)