S7-200 Specifications
Table A-5
Specifications for CPU 226 DC/DC/DC and CPU 226 AC/DC/Relay (continued)
Description
Order Number
Output Features
Number of integrated outputs
Output type
Output Voltage
Permissible range
Rated value
Logic 1 signal at maximum current
Logic 0 signal with 10 K Ω load
Output Current
Logic 1 signal
Number of output groups
Number of outputs ON (maximum)
Per group - horizontal mounting (maximum)
Per group - vertical mounting (maximum)
Maximum current per common/group
Lamp load
ON state resistance (contact resistance)
Leakage current per point
Surge current
Overload protection
Isolation (Field Side to Logic)
Optical isolation (galvanic)
Isolation resistance
Isolation coil to contact
Isolation between open contacts
In groups of
Inductive Load Clamping
Repetitive
Energy dissipation
2
< 0.5 LI
x switching rate
Clamp voltage limits
Output Delay
Off to On (Q0.0 and Q0.1)
On to Off (Q0.0 and Q0.1)
Off to On (Q0.2 through Q1.7)
On to Off (Q0.2 through Q1.7)
Switching Frequency (Pulse Train
Outputs)
Q0.0 and Q0.1
Relay
Switching delay
Lifetime mechanical (no load)
Lifetime contacts at rated load
Cable Length
Unshielded
Shielded
A-24
CPU 226 DC/DC/DC
6ES7 216-2AD21-0XB0
16 outputs
Solid state-MOSFET
20.4 to 28.8 VDC
24 VDC
20 VDC, minimum
0.1 VDC, maximum
0.75 A
2
16
8
8
6 A
5 W
0.3 Ω
µ
10
A, maximum
8 A for 100 ms, maximum
No
500 VAC for 1 minute
-
-
-
8 points
1 W, all channels
L+ minus 48V
µ
2
s, maximum
µ
10
s, maximum
µ
15
s, maximum
µ
100
s, maximum
20 kHz, maximum
-
-
-
150 m
500 m
S7-200 Programmable Controller System Manual
CPU 226 AC/DC/Relay
6ES7 216-2BD21-0XB0
16 outputs
Relay, dry contact
5 to 30 VDC or 5 to 250 VAC
-
-
-
2.00 A
3
16
4/5/7
4/5/7
10 A
30 W DC/200 W AC
0.2Ω, maximum when new
-
7 A with contacts closed
No
-
100 M Ω, minimum when new
1500 VAC for 1 minute
750 VAC for 1 minute
4 points/5 points/7 points
-
-
-
-
-
-
1 Hz, maximum
10 ms, maximum
10,000,000 open/close cycles
100,000 open/close cycles
150 m
500 m
A5E00066097-02