4.3
Inverse-Time Overcurrent Protection 51(N)
Operating Modes
Three-phase
Two-phase
Measuring Technique
All elements
Setting Ranges / Increments
Pickup currents 51 (phases)
Pickup currents 51N
(ground)
Time multiplier T for 51, 51N
for IEC characteristics
Time multiplier T for 51, 51N
for ANSI characteristics
Trip Time Curves acc. to IEC
Acc. to IEC 60255-3 or BS 142, Section 3.5.2 (see also Figures 4-1 and 4-2)
The tripping times for I/I
For zero sequence current, read 3I0p instead of I
for ground fault, read I
Pickup threshold
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
Standard
Phases A and C
First harmonic, rms value (true rms)
for I
= 1 A 0.10 A to 4.00 A
Nom
for I
= 5 A 0.50 A to 20.00 A
Nom
for I
= 1 A 0.05 A to 4.00 A
Nom
for I
= 5 A 0.25 A to 20.00 A
Nom
≥ 20 are identical with those for I/I
p
instead of I
and T
instead of T
Ep
p
IEp
4.3 Inverse-Time Overcurrent Protection 51(N)
0.05 s to 3.20 s or ∞
(disabled)
0.50 s to 15.00 s or ∞
(disabled)
= 20
p
and T
instead of T
;
p
3I0p
p
p
approx. 1.10 · I
p
Technical Data
Increments 0.01 A
Increments 0.01 A
Increments 0.01 s
Increments 0.01 s
347