Settings - Siemens SIPROTEC 7SK80 Manual

Motor protection
Hide thumbs Also See for SIPROTEC 7SK80:
Table of Contents

Advertisement

2.13.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
VOLTAGE
0
POWER
0
VOLTAGE SYSTEM
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
C
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
df/dt rising
df/dt falling
Binray Input
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Exceeding
Dropping below
Ia
Ib
Ic
In
In sensitive
In2
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Vx
Ia Va-n
Ib Vb-n
Ic Vc-n
Phase-Phase
Phase-Ground
2.13 Flexible Protection Functions
Default Setting
OFF
Flexible Function
3-phase
Mode of Operation
Please select
Selection of Measured
Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Ia
Current
Please select
Voltage
Ia Va-n
Power
Phase-Phase
Voltage System
Functions
Comments
215