2.14.3
Configuring the Reverse Power Protection in DIGSI
First create and open a 7SK80 device in the DIGSI manager. In the scope of functions, a flexible protection
function (flexible function 01) is configured for the present example.
Figure 2-81
Select „Additional Functions" in the „Parameters" menu to view the flexible function. The parameter selection
options for the flexible protection functions primarily depend on the settings made in the Power System Data
1 for the connection of the voltage and current transformers (addresses 213 and 251).
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
Configuration of a flexible protection function
2.14 Reverse-Power Protection Application with Flexible Protection Function
Functions
223