Addr.
Parameter
263
OP.CYCLES Isc
264
Ix EXPONENT
265
Cmd.via control
266
T 52 BREAKTIME
267
T 52 OPENING
276
TEMP. UNIT
280
Holmgr. for Σi
613A
Gnd O/Cprot. w.
614A
OP. QUANTITY 59
615A
OP. QUANTITY 27
2.1.3.4 Information List
No.
Information
5145
>Reverse Rot.
5147
Rotation ABC
5148
Rotation ACB
10036
Capac.Par.Fail.
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
C
Setting Options
1 .. 1000
1.0 .. 3.0
(Setting options depend
on configuration)
1 .. 600 ms
1 .. 500 ms
Celsius
Fahrenheit
NO
YES
Ignd (measured)
3I0 (calcul.)
Vphph
Vph-n
V1
V2
V1
Vphph
Vph-n
Type of In-
formation
SP
>Reverse Phase Rotation
OUT
Phase rotation ABC
OUT
Phase rotation ACB
OUT
Malparameteriz. Volt.-divider Capacities
Default Setting
50
Switch. Cycles at Rated
Short-Cir. Curr.
2.0
Exponent for the Ix-Method
None
52 B.Wear: Open Cmd. via
Control Device
80 ms
Breaktime (52 Breaker)
65 ms
Opening Time (52 Breaker)
Celsius
Unit of temperature mea-
surement
NO
Holmgreen-conn. (for fast
sum-i-monit.)
Ignd (measured)
Ground Overcurrent protec-
tion with
Vphph
Opera. Quantity for 59 Ov-
ervolt. Prot.
V1
Opera. Quantity for 27 Und-
ervolt. Prot.
Comments
Functions
2.1 General
Comments