Functions
2.18 Auxiliary Functions
2.18.8
Energy Metering
Metered values for active and reactive energy are determined by the device. They can be output via the display
of the device, read out with DIGSI via the operator interface or transmitted to a control center via port B.
2.18.8.1 Description
Metered Values for Active and Reactive Energy
Metered values of the real power W
hours primary or in kVARh, MVARh or GVARh primary, separately according to the input (+) and output (–), or
capacitive and inductive. The measured-value resolution can be configured. The signs of the measured values
appear as configured in address 1108 P,Q sign (see Section „Display of Measured Values").
2.18.8.2 Setting Notes
Setting of parameter for meter resolution
Parameter 8315 MeterResolution can be used to maximize the resolution of the metered energy values by
Factor 10 or Factor 100 compared to the Standard setting.
2.18.8.3 Settings
Addr.
Parameter
8315
MeterResolution
2.18.8.4 Information List
No.
Information
-
Meter res
888
Wp(puls)
889
Wq(puls)
916
WpΔ=
917
WqΔ=
924
WpForward
925
WqForward
928
WpReverse
929
WqReverse
266
and reactive power (W
p
Setting Options
Standard
Factor 10
Factor 100
Type of In-
formation
IntSP_Ev
Reset meter
PMV
Pulsed Energy Wp (active)
PMV
Pulsed Energy Wq (reactive)
-
Increment of active energy
-
Increment of reactive energy
MVMV
Wp Forward
MVMV
Wq Forward
MVMV
Wp Reverse
MVMV
Wq Reverse
) are acquired in kilowatt, megawatt or gigawatt
q
Default Setting
Standard
Meter resolution
Comments
E50417-G1140-C344-A4, Release date 08.2010
Comments
SIPROTEC, 7SK80, Manual