hit counter script

Negative Sequence Protection 46; Definite Time Characteristic - Siemens SIPROTEC 7SK80 Manual

Motor protection
Hide thumbs Also See for SIPROTEC 7SK80:
Table of Contents

Advertisement

2.6

Negative Sequence Protection 46

Negative sequence protection detects unbalanced loads on the system.
Applications
• The application of unbalanced load protection to motors has a special significance. Unbalanced loads create
counter-rotating fields in three-phase induction motors, which act on the rotor at double frequency. Eddy cur-
rents are induced at the rotor surface, and local overheating in rotor end zones and the slot wedge begins
to take place. This especially goes for motors which are tripped via vacuum contactors with fuses connected
in series. With single-phasing by fuse pickup the motor only generates small and pulsing moments such that
it soon gets strained thermally assuming, however, that the driven machine requires the same amount of
moments. In addition, with unbalanced supply voltage it is endangered by thermal overload. Due to the small
negative sequence reactance even small voltage asymmetries lead to negative sequence currents.
• In addition, this protection function may be used to detect interruptions, short circuits and polarity problems
with current transformers.
• It is also useful in detecting single-phase and two-phase faults with fault currents lower than the maximum
load currents.
Prerequisites
The unbalanced load protection becomes effective when:
a minimum phase current is larger than 0.1 x I
all phase currents are smaller than 10 x I
2.6.1

Definite Time Characteristic

The definite time characteristic consists of two elements. As soon as the first settable threshold 46-1 PICKUP
is reached, a pickup message is output and time element 46-1 DELAY is started. When the second Element
46-2 PICKUP is started, another message is output and time element 46-2 DELAY is initiated. Once either
time delay elapses, a trip signal is initiated.
Figure 2-30
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
Nom
Definite time characteristic for negative sequence protection
and
Nom
.
Functions
2.6 Negative Sequence Protection 46
111

Advertisement

Table of Contents
loading

Table of Contents