2.5.5
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5015
59-1 PICKUP V2
5016
59-2 PICKUP V2
5017A
59-1 DOUT RATIO
5018A
59-2 DOUT RATIO
5019
59-1 PICKUP V1
5020
59-2 PICKUP V1
5101
FCT 27
5102
27-1 PICKUP
5103
27-1 PICKUP
5106
27-1 DELAY
5110
27-2 PICKUP
5111
27-2 PICKUP
5112
27-2 DELAY
5113A
27-1 DOUT RATIO
5114A
27-2 DOUT RATIO
5120A
CURRENT SUPERV.
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
Setting Options
OFF
ON
Alarm Only
20 .. 260 V
20 .. 150 V
0.00 .. 100.00 sec; ∞
20 .. 260 V
20 .. 150 V
0.00 .. 100.00 sec; ∞
2 .. 150 V
2 .. 150 V
0.90 .. 0.99
0.90 .. 0.99
20 .. 150 V
20 .. 150 V
OFF
ON
Alarm Only
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
1.01 .. 3.00
1.01 .. 3.00
OFF
ON
Default Setting
OFF
59 Overvoltage Protection
110 V
59-1 Pickup
110 V
59-1 Pickup
0.50 sec
59-1 Time Delay
120 V
59-2 Pickup
120 V
59-2 Pickup
0.50 sec
59-2 Time Delay
30 V
59-1 Pickup V2
50 V
59-2 Pickup V2
0.95
59-1 Dropout Ratio
0.95
59-2 Dropout Ratio
110 V
59-1 Pickup V1
120 V
59-2 Pickup V1
OFF
27 Undervoltage Protection
75 V
27-1 Pickup
45 V
27-1 Pickup
1.50 sec
27-1 Time Delay
70 V
27-2 Pickup
40 V
27-2 Pickup
0.50 sec
27-2 Time Delay
1.20
27-1 Dropout Ratio
1.20
27-2 Dropout Ratio
ON
Current Supervision
Functions
2.5 Voltage Protection 27, 59
Comments
109