Bus Error Messages - IBM 8677 - BladeCenter Rack-mountable - Power Supply Hardware Maintenance Manual And Troubleshooting Manual

Hardware maintenance manual
Hide thumbs Also See for 8677 - BladeCenter Rack-mountable - Power Supply:
Table of Contents

Advertisement

Note: See Chapter 7, "Parts listing, BladeCenter Type 8677 and 1881," on page 77 to determine which components
should be replaced by a field service technician.
Message
Remote access attempt failed. Invalid
userid or password received. User is
XXX from WEB browser
IP@=XXX.XXX.XXX.XXX
DHCP [X] failure, no IP @ assigned (retry
X), rc=X
LAN: Command mode tamper triggered.
Possible break in attempt.
LAN: WEB server tamper delay
triggered. Possible break in attempt.
System log cleared.

Bus error messages

Note: See Chapter 7, "Parts listing, BladeCenter Type 8677 and 1881," on page 77 to determine which components
should be replaced by a field service technician.
Message
Failure reading I2C device. Check
devices on bus 1.
Failure reading I2C device. Check
devices on bus 2.
Failure reading I2C device. Check
devices on bus 3.
Failure reading I2C device. Check
devices on bus 4.
74
BladeCenter E Type 8677 and 1881: Hardware Maintenance Manual and Troubleshooting Guide
Action
Failed attempt to log into the management module.
Failed to get IP address by DHCP server. Check the DHCP server
connection and settings.
Unsuccessful attempt to access the management module in
command mode. Information only. Take action as required.
Unsuccessful attempt to access the management module in
command mode. Information only. Take action as required.
Information only. Take action as required.
Action
1. Reset the management module.
2. Reseat the management module.
3. Reflash the management module.
4. Replace the management module.
1. Reset the management module.
2. Reseat the management module.
3. Replace the management module.
4. Replace the midplane.
1. Reseat the power modules.
2. Reseat the management module.
3. Replace the power modules.
4. Replace the management module.
5. Replace the midplane.
1. Reseat the management module.
2. Reseat the cables connected to the front panel customer interface
card.
3. Reseat the cables connected to the rear panel customer interface
card.
4. Replace the front panel customer interface card.
5. Replace the rear panel customer interface card.
6. Replace the management module.
7. Replace the midplane.