Note: See "System" on page 116 to determine which components a field service technician should replace.
Message
System over temperature for CPU x
(level-warning; CPU x reporting over
temperature condition)
System under recommended CPU x
temperature (level-warning; system
reporting under temperature condition for
CPU x)
Fan error messages
Note: See "System" on page 116 to determine which components a field service technician should replace.
Message
Fan x failure (level-critical; fan x had a
failure)
Fan x fault (level-critical; fan x beyond
recommended RPM range)
Fan x outside recommended speed
action
Power error messages
Note: See "System" on page 116 to determine which components a field service technician should replace.
Message
Power supply x current share fault
(level-critical; excessive current demand on
power supply x)
Power supply x DC good fault
(level-critical; power good signal not detected
for power supply x)
Power supply x temperature fault
Power supply x removed
Power supply x fan fault (level-critical; fan
fault in power supply x)
Power supply x 12 V fault (level-critical;
overcurrent condition detected)
Power supply x 3.3 V fault (level-critical;
3.3 V power supply x had an error)
Power supply x 5 V fault (level-critical; 5 V
power supply x had an error)
System running non-redundant power
(level-noncritical; system does not have
redundant power)
Action
Ensure that the server is being properly cooled; see "System
reliability considerations" on page 41.
Ambient temperature must be within normal operating
specifications; see "Features and specifications" on page 3.
Action
1. Check connections to fan x.
2. Replace fan x.
1. Check connections to fan x.
2. Replace fan x.
Replace fan x.
Action
Replace power supply x.
Replace power supply x.
Replace power supply x.
No action required - information only.
Replace power supply x.
See "Power checkout" on page 37.
See "Power checkout" on page 37.
See "Power checkout" on page 37.
1. Add another power supply.
2. Remove options from server.
3. System can continue to operate without redundancy protection if
steps 1 and 2 are not followed.
Chapter 6. Symptom-to-FRU index
109