Functions
2.27 Jump of Voltage Vector
Time Delays
The time delay T DELTA PHI (address 4603) should be left at zero, unless you wish to transmit the trip indi-
cation with a delay to a logic (CFC), or to leave enough time for an external blocking to take effect.
After expiry of the timer T RESET (address 4604), the protection function is automatically reset. The reset time
depends on the decoupling policy. It must have expired before the circuit breaker is reclosed. Where the auto-
matic reset function is not used, the timer is set to ∞. The reset signal must come in this case from the binary
input (circuit breaker auxiliary contact).
The timer T BLOCK with reset delay (address 4607) helps to avoid overfunctioning when voltages are connect-
ed or disconnected. Normally the default setting need not be changed. Any change can be performed with the
DIGSI communication software (advanced parameters). It must be kept in mind that T BLOCK should always
be set to more than the measuring window for vector jump measurement (2 cycles).
2.27.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
4601
VECTOR JUMP
4602
DELTA PHI
4603
T DELTA PHI
4604
T RESET
4605A
U MIN
4606A
U MAX
4607A
T BLOCK
2.27.4
Information List
No.
Information
5581
>VEC JUMP block
5582
VEC JUMP OFF
5583
VEC JMP BLOCKED
5584
VEC JUMP ACTIVE
5585
VEC JUMP Range
5586
VEC JUMP pickup
5587
VEC JUMP TRIP
202
Setting Options
OFF
ON
Block relay
2 .. 30 °
0.00 .. 60.00 sec; ∞
0.10 .. 60.00 sec; ∞
10.0 .. 125.0 V
10.0 .. 170.0 V
0.00 .. 60.00 sec; ∞
Type of In-
formation
SP
>BLOCK Vector Jump
OUT
Vector Jump is switched OFF
OUT
Vector Jump is BLOCKED
OUT
Vector Jump is ACTIVE
OUT
Vector Jump not in measurement range
OUT
Vector Jump picked up
OUT
Vector Jump TRIP
Default Setting
OFF
Jump of Voltage Vector
10 °
Jump of Phasor DELTA PHI
0.00 sec
T DELTA PHI Time Delay
5.00 sec
Reset Time after Trip
80.0 V
Minimal Operation Voltage U MIN
130.0 V
Maximal Operation Voltage U
MAX
0.10 sec
Time Delay of Blocking
Comments
C53000-G1176-C149-7, Release date 03.2010
Comments
SIPROTEC, 7UM62, Manual