Functions
2.17 Reverse Power Protection (ANSI 32R)
2.17.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
3101
REVERSE POWER
3102
P> REVERSE
3103
T-SV-OPEN
3104
T-SV-CLOSED
3105A
T-HOLD
2.17.4
Information List
No.
Information
5083
>Pr BLOCK
5086
>SV tripped
5091
Pr OFF
5092
Pr BLOCKED
5093
Pr ACTIVE
5096
Pr picked up
5097
Pr TRIP
5098
Pr+SV TRIP
148
Setting Options
OFF
ON
Block relay
-30.00 .. -0.50 %
0.00 .. 60.00 sec; ∞
0.00 .. 60.00 sec; ∞
0.00 .. 60.00 sec; ∞
Type of In-
formation
SP
>BLOCK reverse power protection
SP
>Stop valve tripped
OUT
Reverse power prot. is switched OFF
OUT
Reverse power protection is BLOCKED
OUT
Reverse power protection is ACTIVE
OUT
Reverse power: picked up
OUT
Reverse power: TRIP
OUT
Reverse power: TRIP with stop valve
Default Setting
OFF
Reverse Power Protection
-1.93 %
P> Reverse Pickup
10.00 sec
Time Delay Long (without Stop
Valve)
1.00 sec
Time Delay Short (with Stop
Valve)
0.00 sec
Pickup Holding Time
Comments
C53000-G1176-C149-7, Release date 03.2010
Comments
SIPROTEC, 7UM62, Manual