hit counter script

Setting Notes - Siemens SIPROTEC 7UM62 Manual

Multifunctional machine protection
Hide thumbs Also See for SIPROTEC 7UM62:
Table of Contents

Advertisement

Functions
2.18 Forward Active Power Supervision (ANSI 32F)
2.18.2

Setting Notes

General
Forward active power protection is only effective and available if this function was set during protective function
configuration (Section 2.4, address 132, FORWARD POWER is set to Enabled). If the function is not required
Disabled is set. The address 3201 FORWARD POWER serves to switch the function ON or OFF or to block only
the trip command (Block relay).
Pickup Values, Time Delays
The setting of the forward power protection depends strongly on the intended purpose. General setting guide-
lines are not possible. The pickup values are set in percent of the secondary apparent power rating S
· U
· I
. Consequently, the machine power must be converted to secondary quantities:
Nsec
Nsec
with
P
sec
S
Nsec
P
Mach
S
N, Mach
U
N Mach
I
N Mach
U
N prim
I
N prim
Address 3202 serves to set the threshold of the forward power to an undershoot (Pf<) and address 3203 (Pf>)
serves to set it to overshoot. Addresses 3204 T-Pf< and 3205 T-Pf> serve to set the associated time delays.
In address 3206 MEAS. METHOD the user can select whether a fast or a precise measuring procedure is to be
used for the forward power calculation. In most cases, the precise measuring procedure is preferred in the
power station sector (as a rule), whereas the fast procedure is applied for use as mains decoupling.
The set times are additional delay times not including the operating times (measuring time, dropout time) of the
protective function.
150
Secondary power corresponding to setting value
secondary nominal power = √3 · U
Machine power corresponding to setting value
Nominal apparent power of the machine
Nominal voltage of the machine
Nominal current of the machine
Primary Nominal Voltage of the voltage transformers
Primary nominal current of the current transformer
· I
Nsec
Nsec
C53000-G1176-C149-7, Release date 03.2010
= √3
Nsec
SIPROTEC, 7UM62, Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents