Getting Started
3.1
Unpacking and repacking of devices and modules
3-2
The devices and modules are packed in the factory such that the requirements of
IEC 60255-21 are fulfilled.
Unpacking and repacking must be performed with the usual care, without force and
only with the aid of suitable tools. The devices and modules must be visually checked
to ensure that they have not been mechanically damaged.
Please observe the instruction leaflet and any other documentation that may be part
of the delivery.
The shipping packaging can be reused in the same manner for further shipment. If oth-
er packaging is used, shock requirements under IEC 60255-21-1 Class 2 and
IEC 60255-21-2 Class 1 must be met.
The devices and modules should be in the final operating area for a minimum of two
hours before the power source is first applied. This time allows the device to attain
temperature equilibrium, and prevents dampness and condensation.
7SS60 Manual
E50417-G1176-C132-A2