Technical Data
9.2
Electrical tests
CE conformity,
regulations
Insulation tests
Standards:
IEC 60255-5;
ANSI/IEEE C37.90.0
EMC tests against
radio disturbances
(type tests)
IEC 60255-6,
IEC 60255-22
(international product
standards)
EN 50082-2 (technical
generic standard)
DIN VDE 57435 part
303 (German product
standard for protection
devices)
9-10
This product complies with the directive of
the Council of the European Communities
on the approximation of the laws of the
member states relating to electromagnetic
compatibility (EMC Council Directive 89/
336/EEC) and concerning electrical
equipment for use within certain voltage
limits (Low-voltage Directive 73/23/EEC).
The product conforms with international
standards of series
IEC 60255 and the German standard DIN
57 435 /Part 303.
This product was developed and
manufactured for utilization in industrial
installations according to the EMC
standards.
High voltage test (routine test),
measuring input I
and relay outputs
d
High voltage test (routine test), auxiliary
voltage input and RS485 interface, binary
inputs and measuring input I
Impulse voltage test (type test), all circuits,
class III
High-frequency test
IEC 60255-22-1,
DIN VDE 0435 part 303;
class III
Discharge of static electricity
IEC 60255-22-2; IEC 61000-4-2; Klasse III
Exposure to HF field, non-modulated
IEC 60255-22-3 (report); class III
Exposure to HF field, amplitude-modulated
IEC 61000-4-3; class III
Exposure to HF field, pulse-modulated
IEC 61000-4-3/ENV 50204; class III
Fast transient disturbance / burst
IEC 60255-22-4; IEC 61000-4-4; class III
This conformity is proved by tests conducted
by Siemens AG in accordance with Article 10
of the Council Directive in agreement with the
generic standards EN 50081 and EN 50082
for EMC directive, and with the standards
EN 60255-6 for the low-voltage directive.
2.5 kV (rms); 50 Hz
3.5 kVdc
R
5 kV (peak); 1.2/50 µs; 0.5 J;
3 positive and 3 negative
pulses in intervals of 5 s
2.5 kV (peak); 1 MHz; t = 15 µs;
400 pulses per s; test duration 2 s
8 kV discharge of contacts; 15 kV discharge
into air; both polarities; 150 pF; R
10 V/m; 27 to 500 MHz
10 V/m; 80 to 1 000 MHz; 80 % AM;
1 kHz
10 V/m; 900 MHz;
repetition frequency 200 Hz; ED 50 %
4 kHz; 5/50 ns; 5 kHz, burst duration =
15 ms; repetition rate 300 ms; both polarities;
= 50 Ω; test duration 1 min
R
l
= 330 Ω
l
7SS60 Manual
E50417–G1176–C132–A2