5.3.2
Hints on setting
Rated system
frequency
Lockout function
5.3.3
Overview of parameters
DIGSI
Parameter
addr.
1101
01 FREQ
1134
01 T-TRP
1135
01 L.Out
5.3.4
Annunciations
FNo.
Text on LC display
7721
LockOut
7SS60 Manual
E50417-G1176-C132-A2
The default setting is +]; it needs to be changed only for a system frequency of
+].
16.7 Hz are available in a version with separate order no.
Note:
The parameter )5(4 () can only be called up in versions for 50 Hz or 60 Hz.
In systems with a rated frequency of 16.7 Hz, the parameter )5(4 () is not
displayed at all.
If the Lockout function is set to 21, the lockout state can only be reset via a binary
input. If 21EXWW is set, the lockout can be reset with the N key or with a binary input.
Possible settings
50 Hz
60 Hz
0.01 s to 32.00 s
OFF
ON
ON/key
Lockout state
Default setting
50 Hz
Rated frequency of power system
0.15 s
Minimum duration of TRIP command
OFF
Lockout function
Logical functions
Functions
Explanation
5-15